Wiring Requirements 

 

WARNING 

Safety First 

Turn the power off before disconnecting modules or wires. The 
correct power supply voltage is listed on the product label. Check 
the voltage of your power source to make sure that you are using 
the correct voltage. Do NOT use a voltage greater than what is 
specified on the product label 
Calculate the maximum possible current in each power wire and 
common wire. Observe all electrical codes dictating the 
maximum current allowable for each wire size. If the current goes 
above the maximum ratings, the wiring could overheat, causing 
serious damage to your equipment. 

 

You should also pay attention to the following points: 

 

Use separate paths to route wiring for power and devices. If power 
wiring and device wiring paths must cross, make sure the wires are 
perpendicular at the intersection point. 
NOTE: Do not run signal or communications wiring and power wiring 
in the same wire conduit. To avoid interference, wires with different 
signal characteristics should be routed separately. 

 

You can use the type of signal transmitted through a wire to 
determine which wires should be kept separate. The rule of thumb is 
that wiring that shares similar electrical characteristics can be 
bundled together. 

 

Keep input wiring and output wiring separated. 

 

It is strongly advised that you label wiring to all devices in the system 
when necessary. 

Grounding the EtherDevice Switch 

Grounding and wire routing help limit the effects of noise due to 
electromagnetic interference (EMI). Run the ground connection from the 
ground screw to the grounding surface prior to connecting devices. 

 

ATTENTION 

This product is intended to be mounted to a well-grounded 
mounting surface such as a metal panel. 

 

Wiring the Redundant Power Inputs 

The two 2-contact terminal block connectors on the EDS's top panel are 
used for the EDS's two DC power inputs. Top and front views of the 
terminal block connectors are shown here. 

Summary of Contents for EtherDevice EDS-G205A-4PoE

Page 1: ... 2011 Moxa Inc All rights reserved P N 1802002051020 EDS G205A 4PoE Hardware Installation Guide Moxa EtherDevice Switch First Edition October 2011 ...

Page 2: ... mounting capability and IP30 metal housing with LED indicators make the plug and play EDS G205A 4PoE switches reliable and easy to use NOTE Throughout this Hardware Installation Guide we use EDS as an abbreviation for Moxa EtherDevice Switch EDS Moxa EtherDevice Switch Package Checklist Your EDS is shipped with the following items If any of these items is missing or damaged please contact your cu...

Page 3: ...D 4 PoE status LED 5 10 100 1000Base T X PoE ports port 2 3 4 5 6 TP port speed LED 7 10 100 1000Base T X port port 1 8 10 100 1000Base X SFP slot 9 Model name 10 Grounding screw 11 P1 power input terminal block 12 P2 power input terminal block 13 DIP switches 14 Screw holes for panel mounting kit 15 DIN Rail mounting kit ...

Page 4: ...EDS when you take it out of the box If you need to reattach the DIN Rail attachment plate make sure the stiff metal spring is situated towards the top as shown in the figures below STEP 1 Insert the top of the DIN Rail into the slot just below the stiff metal spring STEP 2 The DIN Rail attachment unit will snap into place as shown below ...

Page 5: ...ct locations of the 4 screws The heads of the screws should be less than 6 0 mm in diameter and the shafts should be less than 3 5 mm in diameter as shown in the figure at the right NOTE Before tightening the screws into the wall make sure the screw head and shank size are suitable by inserting the screw into one of the keyhole shaped apertures of the wall mounting plates Do not screw the screws i...

Page 6: ... communications wiring and power wiring in the same wire conduit To avoid interference wires with different signal characteristics should be routed separately You can use the type of signal transmitted through a wire to determine which wires should be kept separate The rule of thumb is that wiring that shares similar electrical characteristics can be bundled together Keep input wiring and output w...

Page 7: ...ge is stable Communication Connections The EDS P205A 4PoE switches have 4 10 100 1000Base T X PoE Ethernet ports for connecting PoE devices and 1 10 100 1000Base T port or 1 1000Base X SFP slot for uplink connection 10 100 1000Base T X Ethernet Port Connection 10 100 1000Base T X ports located on the EDS s front panel are used to connect to Ethernet enabled devices Below we show pinouts for both M...

Page 8: ...E enabled devices The pinout follows the Alternative A MDI mode of 802 3af 802 3at standards Please see the details in the following table PoE Port Pinout Pin Power 8 pin RJ45 1 V 2 V 3 V 6 V NOTE According to IEEE 802 3af at standards the PD shall be implemented to be insensitive to the polarity of the power supply and shall be able to operate per MDI mode and MDI X mode However some PDs only sup...

Page 9: ...hoose a straight through Ethernet cable between the PD and the EDS switch Redundant Power Inputs Both power inputs can be connected simultaneously to live DC power sources If one power source fails the other live source acts as a backup and automatically supplies all of the EDS s power needs DIP Switch Settings The default setting for each DIP Switch is OFF The following table explains the effect ...

Page 10: ...ed to power input P2 10 100 1000 AMBER On TP port s 10 100 Mbps link is active Blinking Data is being transmitted at 10 100 Mbps Off TP Port s 10 100 Mbps link is inactive GREEN On TP port s 1000 Mbps link is active Blinking Data is being transmitted at 1000 Mbps Off TP Port s 1000 Mbps link is inactive 1000 GREEN On SFP module s 1000Mbps link is active Blinking Data is being transmitted at 1000 M...

Page 11: ...r during maintenance The half full duplex mode for the switched RJ45 ports is user dependent and changes by auto negotiation to full or half duplex depending on which transmission speed is supported by the attached device Jumbo Frame By default EDS G205A 4PoE series supports Ethernet jumbo frame up to 9 6K which is with more than 1500 bytes of payload This is commonly used for large packet size ap...

Page 12: ...Protection Present Conformance to UL standards Always use an isolated power supply to conform to the UL 508 standard Note We strongly recommend using an isolated power supply with maximum output current of 7 5 A due to the power de rating issue of the power supply at high operating temperatures Moreover without galvanic isolation between the redundant power inputs of this device the V1 and V2 shou...

Page 13: ...ears Details www moxa com warranty Technical Support Contact Information www moxa com support Moxa Americas Toll free 1 888 669 2872 Tel 1 714 528 6777 Fax 1 714 528 6778 Moxa Europe Tel 49 89 3 70 03 99 0 Fax 49 89 3 70 03 99 99 Moxa Asia Pacific Tel 886 2 8919 1230 Fax 886 2 8919 1231 Moxa China Beijing office Tel 86 10 6872 3959 60 61 Fax 86 10 6872 3958 ...

Reviews: