ioLogik W5300
SMS Commands
B-5
EXP_DEV_RTDType_CH
Read
Expansion RTD Type
DEV=Device slot number, start index:01
CH = Channel number, start index:00
EXP_DEV_RTDUnit_CH
Read
Expansion RTD Unit, C/F or Ohm
DEV=Device slot number, start index:01
CH = Channel number, start index:00
EXP_DEV_TCValue_CH
Read
Expansion TC Value
DEV=Device slot number, start index:01
CH = Channel number, start index:00
EXP_DEV_TCType_CH
Read
Expansion TC Type
DEV=Device slot number, start index:01
CH = Channel number, start index:00
EXP_DEV_TCUnit_CH
Read
Expansion TC Unit, C/F, or mV.
DEV=Device slot number, start index:01
CH = Channel number, start index:00
Example:
1.
Query 1st AI channel of the expansion iologik E1240(8AI) in the 1st slot of the ioLogik W5300 system:
#GetSMS?EXP_01_AIValue_00=?#
2.
Configure the output of the expansion ioLogik E1241(4AO) in the 3rd slot of the ioLogik W5300 system:
#SetSMS?EXP_03_AOValue_00=1023#
Internal Registers (Integer):
SMS Command
Attribute
Note
IR_CH
Read/Write Internal Registers,
CH= Channel Number, Range: 00 to 23. Content: 0 to 255
Example:
1.
Configure the 1st internal register (IR_00) to 128:
#SetSMS?IR_00=128#
Optional Commands:
SMS Command
Attribute
Note
pwd=”password”
Attach Console Password
Due=Date
Attach an expiration date, format: Date
Format: YYYYMMDDHHMM
SAVE_RESTART
Restart the ioLogik device
Details:
1.
Option commands should be combined with the GetSMS?, SetSMS? Commands, and “<””>” signs at the
beginning of the entire command line..
2.
Console passwords should be included with double quotation marks (“)
3.
Multiple Option commands can be integrated using a “:” sign
Example:
1.
Attaching the console password:
#SetSMS<pwd=”admin”>?DOStatus_03=1#
2.
Attaching an expiration date:
#SetSMS<DUE=201102180955>?DOStatus_03=1#
3.
Attaching the console password and an expiration date:
#SetSMS<DUE=201102180955:pwd=”admin”>?DOStatus_03=1#
4.
Restart ioLogik W5300 by SMS command:
#SetSMS<SAVE_RESTART>