ioLogik W5300
Utility: ioAdmin
3-16
desired mode in the
I/O Direction
field under
Power On Settings
. After clicking
Apply
, you will need to
restart the ioLogik W5300 for the new setting to take effect.
Configuring Digital Input Channels
The ioLogik W5300 can provide up to 12 digital
input (DI) channels. To configure software filtering
for a channel, set the
Mode
dropdown in section 1
Mode Settings
to
Filter
. Software filtering is used
to avoid switch bounces. The filter is configurable in
multiples of 0.5 ms and accepts values between 1
and 65535. For example, a setting of
100
would
mean a 50 ms filter (100 × 0.5 ms).
The
Mode
dropdown may also be used to set the channel as straight
Input (DI),
or as an
Event Counter
.
Type
On
Off
Dry contact
Short to GND
Open
Wet contact
0 to 3 VDC
10 to 30 VDC
When set as an
Event Counter
, the channel will accept limit or proximity switches, and will tabulate ON/OFF
signal events. When
Lo to Hi
is selected, the counter value increases when an attached switch/circuit is closed.
When
Hi to Lo
is selected, the counter value increases when an attached switch/circuit is released. When
Both
is selected, the counter value increases when attached the switch/circuit is successively closed and opened.