- 6 - 

Modbus Serial Port (Male DB9) 

Pin  RS-232 

RS-422/ 

RS-485 (4W) 

RS-485 (2W) 

DCD 

TxD-(A) 

– 

RXD 

TxD+(B) 

– 

TXD 

RxD+(B) 

Data+(B) 

DTR 

RxD-(A) 

Data-(A) 

  5* 

GND 

GND 

GND 

DSR 

– 

– 

RTS 

– 

– 

CTS 

– 

– 

– 

– 

– 

 

 

*Signal ground 

PROFIBUS Serial Port (Female DB9) 

Pin 

Signal   

PROFIBUS D+ 

RTS 

Signal common 

5V 

PROFIBUS D- 

 

 

Console Port (RS-232) 

The MGate 5111 Series can use an RJ45 serial port to connect to a PC to 
configure the device. 

Pin 

Signal 

DSR 

RTS 

GND 

TXD 

RXD 

DCD 

CTS 

DTR 

 

 

Power Input and Relay Output Pinouts 

 

 

V2+ 

V2- 

 

V1+ 

V1- 

Shielded 

Ground 

DC 

Power 

Input 2 

DC 

Power 

Input 2 

N.O.  Common 

N.C. 

DC 

Power 

Input 1 

DC 

Power 

Input 1 

 
 

Summary of Contents for MGate 5111

Page 1: ...ericas Toll free 1 888 669 2872 Tel 1 714 528 6777 Fax 1 714 528 6778 Moxa China Shanghai office Toll free 800 820 5036 Tel 86 21 5258 9955 Fax 86 21 5258 5505 Moxa Europe Tel 49 89 3 70 03 99 0 Fax 49 89 3 70 03 99 99 Moxa Asia Pacific Tel 886 2 8919 1230 Fax 886 2 8919 1231 Moxa India Tel 91 80 4172 9088 Fax 91 80 4132 1045 2017 Moxa Inc All rights reserved ...

Page 2: ... 51 mm wide Hardware Introduction LED Indicators LED Color Description PWR 1 PWR 2 Green Power is on Off Power is off Ready Green Steady on Power is on and the unit is functioning normally Blinking The unit is responding to the software s Locate function Red Steady on Power is on and the unit is booting up Blinking Indicates an IP conflict or the DHCP or BOOTP server is not responding properly Fla...

Page 3: ...d Flashing only A communication error occurred Master Mode 1 Received an exception code or framing error parity error checksum error 2 Command timeout the slave device is not responding Slave Mode 1 Received an invalid function code or framing error parity error checksum error 2 Accessed invalid register address or coil address Off No communication PBS Green Flashing only PROFIBUS is receiving or ...

Page 4: ...anel you will find DIP switches to adjust each serial port s pull up resistor pull down resistor and terminator SW MODBUS 1 2 3 Pull up resistor Pull down resistor Terminator ON 1 kΩ 1 kΩ 120 Ω OFF 150 kΩ default 150 kΩ default default Rotary Switch Before communicating you must assign a slave ID to the PROFIBUS slave If you would like to assign an address between 0 to 99 you need to change the ro...

Page 5: ...he spring and properly attach it to the DIN rail until it snaps into place For wall mounting install the wall mount kit optional first and then screw the device onto the wall The following figure illustrates the two mounting options Software Installation Information Please download the user s manual and DSU Device Search Utility from Moxa s website www moxa com Insert the CD and follow the on scre...

Page 6: ...Female DB9 Pin Signal 1 2 3 PROFIBUS D 4 RTS 5 Signal common 6 5V 7 8 PROFIBUS D 9 Console Port RS 232 The MGate 5111 Series can use an RJ45 serial port to connect to a PC to configure the device Pin Signal 1 DSR 2 RTS 3 GND 4 TXD 5 RXD 6 DCD 7 CTS 8 DTR Power Input and Relay Output Pinouts V2 V2 V1 V1 Shielded Ground DC Power Input 2 DC Power Input 2 N O Common N C DC Power Input 1 DC Power Input...

Page 7: ...n a tool accessible IP54 enclosure and use in an area of not more than pollution degree 2 as defined by IEC EN 60664 1 b Conductors suitable for use in an ambient temperature greater than 86 C must be used for the power supply terminal c A 4 mm2 conductor must be used when a connection to the external grounding screw is utilized d Provisions shall be made either in the equipment or external to the...

Page 8: ...vision 2 WARNING EXPOSURE TO SOME CHEMICALS MAY DEGRADE THE SEALING PROPERTIES OF MATERIALS USED IN THE FOLLOWING DEVICE Sealed Relay Device U21 WARNING EXPLOTION HAZARD Indoor use and Pollution degree 2 WARNING EXPLOTION HAZARD The equipment and label must be wiped by a dry cloth WARNING EXPLOTION HAZARD The device may only be connected to the supply voltage connections compliant with UL60950 or ...

Reviews: