- 6 -
Wiring Requirements
WARNING
Turn the power off before disconnecting modules or wires. The
correct power supply voltage is listed on the product label. Check
the voltage of your power source to make sure you are using the
correct voltage. Do NOT use a voltage greater than what is
specified on the product label.
These devices must be supplied by a SELV source as defined in
the Low Voltage Directive 2006/95/EC and 2004/108/EC.
ATTENTION
Safety First!
Be sure to disconnect the power cord before installing and/or
wiring your Moxa switch.
This device has UL508 approval. Use copper conductors only,
60/75°C, and tighten to 4.5 pound-inches. For use in pollution
degree 2 environments.
ATTENTION
Safety First!
Observe all electrical codes dictating the maximum current
allowable for each wire size. If the current goes above the
maximum ratings, the wiring could overheat, causing serious
damage to your equipment.
Be sure to read the following guidelines:
•
Use separate paths to route wiring for power and devices. If power
wiring and device wiring paths must cross, make sure the wires are
perpendicular at the intersection point.
NOTE Do not run signal or communications wiring and power wiring
through the same wire conduit. To avoid interference, wires with
different signal characteristics should be routed separately.
•
You can use the type of signal transmitted through a wire to
determine which wires should be kept separate. The rule of thumb is
that wiring that shares similar electrical characteristics can be
bundled together.
•
Keep input wiring and output wiring separated.
•
We strongly advise that you label wiring for all devices in the system.