Installation and start up
16
Sealing plug
4.4
Water in- and outlets of the device are sealed with plugs to prevent leaks during delivery
(see Figure 7).
Before connecting the system to the water supply and waste water drain, remove the
sealing plugs from the tube connecters on the back side of the device.
-
Remove the retaining ring (1.) from plug connector
-
Depress the plug connector (2.)
and keep it pressed to pull out the sealing plug
(3.)
Figure 7
Connecting
4.5
Figure 8 shows the assignment of the inputs and outputs for all water tubes and electrical
connections.
All waste tubes must be led with a downward gradient toward the waste water drain. Any
reduction of the diameter, loops, siphons or breaks in the line must be avoided.
A minimum safety distance of 2 cm (3/4-inch) must be between tube end and waste water
to prevent siphoning. An air gap of a minimum distance of double inner tube diameter is
recommended.
-
After removing the sealing plugs, insert the tubes into the connectors as far as they
will go
-
Lock the tubes with retaining rings
1. Retaining ring
2. Plug connector
3. Sealing plug