Smoke damper

rev 21-10

installed in single compartment smoke ducts to concentrate all the depression of the smoke extraction 
fan in the smoke reservoirs actually affected by the presence of smoke. This fire protection project shall be 
designed by a fire expert. The products used in system should not be larger than dimension Ø 630. 

Testing and classification

The WXH single compartment smoke control dampers have been tested  connected to single compart-

ment circular ducts and fittings belonging to the Lindab (www.lindab.com) smoke and heat exhaust 

ventilation system. 

WXH smoke control dampers have two relay response options: type AA (Automatic Activation) and type 

MA (Manual Activation).

In accordance with EN12101-8:2011 WXH single compartment smoke control dampers have been subjec-

ted to the following tests:

- Opening and closing cycles according to EN1366-10:2011+A1:2017: 10000 cycles at nominal operating 

supply, 100 cycles at nominal operating supply -10%, 100 cycles at nominal operating 15%.

- Blade and casing ambient leakage according to EN1751:2014 with pressure from -2000Pa to +2000Pa 

obtaining the classification in class 2 for the air tightness of the blade and class C for the air tightness of 

the casing.

- Extraction system ambient leakage according to EN1366-10:2011+A1:2017 with pressure -1500Pa (level 

3).

- 600°C temperature resistance according to EN1366-10:2011+A1:2017 with pressure -500Pa (level 3) 

for 120 minutes with damper installation both horizontal and vertical and with blade rotation axis both 

horizontal and vertical. 

The fire classification obtained according to EN13501-4:2016 is:

According to the classification obtained, according to Tables 1 and 3 (level 3) and according to paragraph 

6.3.2.2 of EN1366-10:2011+A1:2017 it is allowed to use single compartment smoke control dampers WXH:

- In single compartment smoke exhaust ventilation system;

- In general HVAC systems as well as a smoke control system;

- With depression for smoke exhaust up to -500Pa;

- With pressure at ambient temperature from -1500Pa to +500Pa.

E

I

t

Ved

ho

i

o

S

Operating pressure

C

MA/

AA

Single/ 

multi

E6oo -

120 v

ed

h

od

i

o

S

-1500 Pa to 500 Pa

10000

MA

single

E6oo -

120 v

ed

h

od

i

o

S

-1500 Pa to 500 Pa

10000

AA

single

According to par. 9.7.1 of EN1366-10:2011+A1:2017, single compartment smoke control dampers may be 

applied to ducts that have been tested to EN 1366-9, constructed from materials of the same density as 

those tested or of the same material with a greater density or thickness. 

Single compartment smoke control dampers may be applied to builders work (created on site) ducts, 

concrete or aerated concrete ducts and walls, provided that the single compartment smoke control 

damper has been tested on a duct or in a wall constructed from materials of lower density and thickness 

(e.g. boards or sheet steel), provided that the concrete/aerated concrete construction has a thickness that 

complies with the  supporting construction information shown in EN 1363-1 and EN 1366-2 for the time 

period of classification required. Correct fire resisting fasteners to suit the materials shall be used.

Summary of Contents for WXH Series

Page 1: ...CIRCULAR SERIES WXH 1500Pa Cert N 1812 CPR 1189 Technical Manual English WXH SINGLE COMPARTMENT SMOKE CONTROL DAMPER ...

Page 2: ...ng to EN1366 10 and classified according to EN13501 4 The damper is suitable for vertical and horizontal installation in single compartment smoke duct evacuation systems with maximum temperature of 600 C for 2 hours with smoke leakage class S at 1500Pa negative pressure Declaration of performance The damper is CE marked with the declaration of performance according to EN12101 8 as a circular smoke...

Page 3: ... installation both horizontal and vertical and with blade rotation axis both horizontal and vertical The fire classification obtained according to EN13501 4 2016 is According to the classification obtained according to Tables 1 and 3 level 3 and according to paragraph 6 3 2 2 of EN1366 10 2011 A1 2017 it is allowed to use single compartment smoke control dampers WXH In single compartment smoke exh...

Page 4: ... 115 298 9 5 407 12 0 560 115 298 11 0 407 13 5 630 115 298 12 5 407 15 Classification details E600 120 ved hod i S 1500Pa C10000 AA single E integrity Temperature Time ved Installation on duct penetrating a vertical wall hod Installation on duct penetrating a horizontal wall origin of fire is irrelevant Smoke leakage 5 m3 h m2 Maximum negative pressure Motor cycles use in combined smoke control a...

Page 5: ...et immediately Storage The goods should be stored inside and protected to prevent dust debris and humidity to damage the goods Before mounting Before starting the mounting of the damper it is necessary to inspect all components to make sure that they are correct according to the project documentation and to make sure they have not been damaged during transport or storage When handling the products...

Page 6: ...5 mm to support itself weight and to prevent damage to the gasket The damper must be installed on certifi ed and CE marked smoke control system Ø nom Minimum number of fasteners required to achieve sufficient strength 100 630 4 Mounting Technical data for the motors BLE motor BLE24 BLE230 Power supply AC DC 19 2 28 8 V 50 60 Hz AC 198 264 V 50 60 Hz Power consumption 7 5 W 5 W For wire sizing 9 VA...

Page 7: ...of several actuators possible Power consumption and switching thresholds must be observed 2 wire open close control The actuator is overload proof and can thus remain energized even at the end stops Two microswitches with fixed settings are installed in the actuator for indicating the damper end positions The position of the damper blade can be read off on a mechanism position indicator The crank ...

Page 8: ... Periodic inspection and cleaning Periodic inspection shall be performed in accordance with the requirements of the law or by the building regulations or other local regulations In the absence of specific regulations or to their complement in accordance with point 8 3 of the EN 12101 8 standard it is recommended to carry out the following controlactivities at intervals of no more than 6 months exe...

Page 9: ...k that the smoke control damper is in the normal operating position Keep records of all inspections repair activities any problems encountered and their resolution This practice even when not mandatory is very useful in practice Disposal Disposal must be carried out in accordance with national legislation For electrical and electronic parts also refer to EU Directive 2011 65 Type WXH Circular smok...