Smoke damper

rev 21-10

WXHU

SAA

D00

200

Type

Relay response

Motor type

Dimension Ød

Ordering example

Repair

For safety reasons, repair activities involving fire-fighting components must be carried out only by qua-

lified personnel. only original spare parts supplied by the smoke control damper manufacturer must be 

used.

A functional test must be performed after each repair.

At the end of the inspection, cleaning or repair operations, check that the smoke control damper is in the 

normal operating position. Keep records of all inspections, repair activities, any problems encountered 

and their resolution. This practice, even when not mandatory, is very useful in practice.

Disposal

Disposal must be carried out in accordance with national legislation. For electrical and electronic parts 

also refer to EU Directive 2011/65

Type

WXH

Circular smoke damper

Connection

U

EPDM gasket

Relay Response

SAA

Automatic Activation

(Single compartment)

MAS

Manual Activation

(Single compartment)

Motor type

V00

Belimo BLE24 V AC/DC

D00

Belimo BLE230 V AC

Dimension

XYZ

Nominal diameter (mm)

Product code

Summary of Contents for WXH Series

Page 1: ...CIRCULAR SERIES WXH 1500Pa Cert N 1812 CPR 1189 Technical Manual English WXH SINGLE COMPARTMENT SMOKE CONTROL DAMPER ...

Page 2: ...ng to EN1366 10 and classified according to EN13501 4 The damper is suitable for vertical and horizontal installation in single compartment smoke duct evacuation systems with maximum temperature of 600 C for 2 hours with smoke leakage class S at 1500Pa negative pressure Declaration of performance The damper is CE marked with the declaration of performance according to EN12101 8 as a circular smoke...

Page 3: ... installation both horizontal and vertical and with blade rotation axis both horizontal and vertical The fire classification obtained according to EN13501 4 2016 is According to the classification obtained according to Tables 1 and 3 level 3 and according to paragraph 6 3 2 2 of EN1366 10 2011 A1 2017 it is allowed to use single compartment smoke control dampers WXH In single compartment smoke exh...

Page 4: ... 115 298 9 5 407 12 0 560 115 298 11 0 407 13 5 630 115 298 12 5 407 15 Classification details E600 120 ved hod i S 1500Pa C10000 AA single E integrity Temperature Time ved Installation on duct penetrating a vertical wall hod Installation on duct penetrating a horizontal wall origin of fire is irrelevant Smoke leakage 5 m3 h m2 Maximum negative pressure Motor cycles use in combined smoke control a...

Page 5: ...et immediately Storage The goods should be stored inside and protected to prevent dust debris and humidity to damage the goods Before mounting Before starting the mounting of the damper it is necessary to inspect all components to make sure that they are correct according to the project documentation and to make sure they have not been damaged during transport or storage When handling the products...

Page 6: ...5 mm to support itself weight and to prevent damage to the gasket The damper must be installed on certifi ed and CE marked smoke control system Ø nom Minimum number of fasteners required to achieve sufficient strength 100 630 4 Mounting Technical data for the motors BLE motor BLE24 BLE230 Power supply AC DC 19 2 28 8 V 50 60 Hz AC 198 264 V 50 60 Hz Power consumption 7 5 W 5 W For wire sizing 9 VA...

Page 7: ...of several actuators possible Power consumption and switching thresholds must be observed 2 wire open close control The actuator is overload proof and can thus remain energized even at the end stops Two microswitches with fixed settings are installed in the actuator for indicating the damper end positions The position of the damper blade can be read off on a mechanism position indicator The crank ...

Page 8: ... Periodic inspection and cleaning Periodic inspection shall be performed in accordance with the requirements of the law or by the building regulations or other local regulations In the absence of specific regulations or to their complement in accordance with point 8 3 of the EN 12101 8 standard it is recommended to carry out the following controlactivities at intervals of no more than 6 months exe...

Page 9: ...k that the smoke control damper is in the normal operating position Keep records of all inspections repair activities any problems encountered and their resolution This practice even when not mandatory is very useful in practice Disposal Disposal must be carried out in accordance with national legislation For electrical and electronic parts also refer to EU Directive 2011 65 Type WXH Circular smok...

Reviews: