background image

STANDARD

DUAL DISPLAY
PID AUTOTUNE
RAMP-TO-SETPOINT
UL

C

, UL, CE (4810)

AUTO / MANUAL
15 SECURITY OPTIONS
UNIVERSAL INPUT

OPTIONS

DUAL OUTPUT
ALARMS - 15 TYPES
24VDC EXCITATION
Rs485 COMMUNICATIONS

SPECIFICATIONS
1. INPUT

*Thermocouple

J, K, T, E, B, R, S, N ( IPTS68/DIN 43710)

*RTD

Pt100 ohms RTD (DIN 43760/BS 1904 or JIS)

*Linear Voltage (current)

-10 to 60 mV confugurablewith input attenuation

*Range

User configurable

*Accuracy

+/-2C for T/C, _+0.2C for RTD, _+0.05% for Linear input.

*Cold Junction Compenasation  0.1% ambient typical.
*Input Impedance

10M ohms for T/C, 100K ohms for Linear Voltage,
2.7 Ohms for 0 (4)- 20 mA/

*Excitation Current for RTD 0.2mA Max.
*Sample Rate

250mS

2. CONTROL

*Proportional Band

0.0-100.0%

*Rest (Integral)

0-3600 Sec.

*Rate (Derivative)

0-3600 Sec.

*Anti Rest Windup

Inhibit integral action outside Proportion Band

*Ramp Rate

0.0-100.0C / minute.

*Dwell

minutes.

*On-Off

With adjustable hysteresis

*Cycle Time

 0-99 seconds.

*Control Action

Configurable for Direct (cooling) or Reverse (Heating)

3. OUTPUT

*Relay

5A/240VAC  resistive.

*Pulsed Voltage

Isloated 24 VDC 100mA Max.

*Current

Isolated 0 (4) - 20 mA Max load 500 ohms.

*Alarm

Relay output, (SPST) 10A/240VAC resistive.

4. POWER

*Rating

85 - 265 VAC 50/60Hz      5VA max

5. ENVIRONMENTAL

*Operating Temp

-10 - 50C

*Humidity

 - 90%

*Insulation

20M  ohms minimum @ 500VDC

*EMC Emission

EN500081-1:1992, EN55022:1994

*EMC Immunity

EN 50082-1:1992, IEC 801-3, IEC 801-4:1988

*Weight

VT4810 180g,  VT4910 240g, VT9610 240g

S C A L E _ _ _ __ _ _ _ _ _ __ _ _ _ _ _ _ _ _

NOT E: V t4810 - EITH ER  OUT2 or A LM1

TEMPERA

TEMPERA

TEMPERA

TEMPERA

TEMPERATURE CONTR

TURE CONTR

TURE CONTR

TURE CONTR

TURE CONTROLS

OLS

OLS

OLS

OLS

VT10 SERIES

VT10 SERIES

VT10 SERIES

VT10 SERIES

VT10 SERIES