DCA125USI 60 HZ GEN. • OPERATION AND PARTS MANUAL — REV. #1 (03/25/11) — PAGE 15
INSTALLATION
OUTDOOR INSTALLATION
Install the generator in a area that is free of debris,
bystanders, and overhead obstructions. Make sure the
generator is on secure level ground so that it cannot slide
or shift around. Also install the generator in a manner so
that the exhaust will not be discharged in the direction of
nearby homes.
The installation site must be relatively free from moisture
and dust. All electrical equipment should be protected from
excessive moisture. Failure to do will result in deterioration
of the insulation and will result in short circuits and
grounding.
Foreign materials such as dust, sand, lint and abrasive
materials have a tendency to cause excessive wear to
engine and alternator parts.
INDOOR INSTALLATION
Exhaust gases from diesel engines are extremely
poisonous. Whenever an engine is installed indoors the
exhaust fumes must be vented to the outside. The engine
should be installed at least two feet from any outside wall.
Using an exhaust pipe which is too long or too small can
cause excessive back pressure which will cause the engine
to heat excessively and possibly burn the valves.
MOUNTING
The generator must be mounted on a solid foundation (such
as concrete) and set fi rmly on the foundation to isolate
vibration of the generator when it is running. The generator
must set at least 6 inches above the fl oor or grade level (in
accordance to NFPA 110, Chapter 5-4.1).
DO NOT
remove
the metal skids on the bottom of the generator. They are
to resist damage to the bottom of the generator and to
maintain alignment.
CAUTION
Pay close attention to ventilation when operating the
generator inside tunnels and caves. The engine exhaust
contains noxious elements. Engine exhaust must be
routed to a ventilated area.
GENERATOR GROUNDING
To guard against electrical shock and possible damage to
the equipment, it is important to provide a good
EARTH
ground.
Article 250 (Grounding) of the National Electrical Code
(NEC) provides guide lines for proper grounding and
specifi es that the cable ground shall be connected to the
grounding system of the building as close to the point of
cable entry as practical.
NEC articles 250-64(b) and 250-66 set the following
grounding requirements:
1. Use one of the following wire types to connect the
generator to earth ground.
a. Copper - 10 AWG (5.3 mm
2
)
b. Aluminum - 8 AWG (8.4 mm
2
)
2. When grounding the generator (Figure 2) connect the
ground cable between the lock washer and the nut on
the generator and tighten the nut fully. Connect the
other end of the ground cable to earth ground.
3. NEC article 250-52(c) specifi es that the earth ground rod
should be buried a minimum of 8 ft. into the ground.
NOTICE
When connecting the generator to any buildings
electrical system
ALWAYS
consult with a licensed
electrician.
Summary of Contents for DCA125USI
Page 19: ...DCA125USI 60 HZ GEN OPERATION AND PARTS MANUAL REV 1 03 25 11 PAGE 19 NOTES ...
Page 51: ...DCA125USI 60 HZ GEN OPERATION AND PARTS MANUAL REV 1 03 25 11 PAGE 51 NOTES ...
Page 54: ...PAGE 54 DCA125USI 60 HZ GENERATOR OPERATION AND PARTS MANUAL REV 1 03 25 11 GENERATOR ASSY ...
Page 56: ...PAGE 56 DCA125USI 60 HZ GENERATOR OPERATION AND PARTS MANUAL REV 1 03 25 11 CONTROL BOX ASSY ...
Page 68: ...PAGE 68 DCA125USI 60 HZ GENERATOR OPERATION AND PARTS MANUAL REV 1 03 25 11 BATTERY ASSY ...
Page 70: ...PAGE 70 DCA125USI 60 HZ GENERATOR OPERATION AND PARTS MANUAL REV 1 03 25 11 MUFFLER ASSY ...
Page 72: ...PAGE 72 DCA125USI 60 HZ GENERATOR OPERATION AND PARTS MANUAL REV 1 03 25 11 FUEL TANK ASSY ...
Page 82: ...PAGE 82 DCA125USI 60 HZ GENERATOR OPERATION AND PARTS MANUAL REV 1 03 25 11 RUBBER SEALS ASSY ...
Page 89: ...DCA125USI 60 HZ GEN OPERATION AND PARTS MANUAL REV 1 03 25 11 PAGE 89 NOTES ...