DCA-180SSJU — OPERATION AND PARTS MANUAL — REV. #3 (02/01/10) — PAGE 53
1
10.Verify that the
Engine Running
status LED on the MPEC unit
(Figure 46) is
ON
(lit) after the
engine has been started.
3. If any abnor malities exists, the War ning and
Emergency Stop lamps on the Engine Operating Panel
will be lit.
4. Place the
(Figure 43) in the
OFF/RESET
position.
5. Place the Diagnostic ON/OFF switch in the
ON
position. Verify that an Active Fault Code message is
being displayed (Diagnostic Display Panel). The fault
code message will continued to be displayed until the
fault has been corrected. Figure 44 shown below is a
typical example of an active fault code message (Low
Radiator Coolant).
Figure 45. Engine Speed Switch (High)
When the MPEC Control switch is
placed in the manual position,
preheating of the glow plugs will begin
automatically and the preheat
lamp will stay lit until
the glow plugs are warmed. When the preheat
lamp goes off this signals the completion of
the preheating cycle and the starting of the
engine.
NOTE
Preheat Lamp
9. If the engine is running smoothly, place the engine
speed switch (Figure 45) in the
“
”
(up) position.
Figure 44. Active Fault Code Message
6. In a situation where several engine problems occur
simultaneously, the word “
MORE
” appears above the
arrow buttons indicating that there are more fault codes
that need to be viewed. Use the arrow buttons to scroll
to the next active fault code.
If desired, the type of fault code, cause of error and
the countermeasures of the error can be referenced
in a separate engine operator’s manual.
7. Before the engine can be started, the engine fault must
be corrected. Also observe that there are no active
fault codes displayed on the diagnostic panel. If no
fault codes are displayed, place the diagnostic switch
in the
OFF
position.
13. The generator's AC-voltmeter (Figure 48) will display the
generator’s output in
VOLTS
. If the voltage is not within
the specified tolerance, use the voltage adjustment
control knob (Figure 49) to increase or decrease the
desired voltage.
Figure 47. Frequency Meter (Hz)
12. The generator's frequency meter (Figure 47) should be
displaying the 60 cycle output frequency in
HERTZ
.
Figure 46. Engine Running LED (ON)
11. Observe that the Warning and Emergency Stop
lamps on the Engine Operating Panel are
OFF
.
8. To restart the engine due to error codes, place the
in the
MANUAL
position (Figure 43)
Figure 48. Voltmeter
GENERATOR START-UP PROCEDURE (MANUAL)
Summary of Contents for DCA180SSJU WHISPERWATT SERIES
Page 2: ...PAGE 2 DCA 180SSJU OPERATION AND PARTS MANUAL REV 3 02 01 10 PROPOSITION 65 WARNING ...
Page 69: ...DCA 180SSJU OPERATION AND PARTS MANUAL REV 3 02 01 10 PAGE 69 1 NOTES ...
Page 72: ...PAGE 72 DCA 180SSJU OPERATION AND PARTS MANUAL REV 3 02 01 10 GENERATOR ASSY GENERATOR ASSY ...
Page 88: ...PAGE 88 DCA 180SSJU OPERATION AND PARTS MANUAL REV 3 02 01 10 BATTERY ASSY BATTERY ASSY ...
Page 90: ...PAGE 90 DCA 180SSJU OPERATION AND PARTS MANUAL REV 3 02 01 10 MUFFLER ASSY MUFFLER ASSY ...
Page 92: ...PAGE 92 DCA 180SSJU OPERATION AND PARTS MANUAL REV 3 02 01 10 FUEL TANK ASSY FUEL TANK ASSY ...
Page 105: ...DCA 180SSJU OPERATION AND PARTS MANUAL REV 3 02 01 10 PAGE 105 1 NOTES ...