DCA25SSIU4F 60 HZ GENERATOR• OPERATION MANUAL — REV. #4 (01/17/18) — PAGE 25
OUTPUT TERMINAL PANEL CONNECTIONS
3Ø-480/277V UVWO Terminal Output Voltages
1. Place the voltage selector switch in the 3Ø 480/277
position as shown in Figure 22.
Figure 22. Voltage Selector Switch
3Ø-480/277V Position
2. Connect the load wires to the UVWO terminals as
shown in Figure 23.
Figure 23. UVWO Terminal Lugs 3Ø-480V
Connections
NOTICE
ALWAYS make sure that the connections to the UVWO
terminals are
secure and tight. The possibility of arcing
exists, that could cause a fire.
1Ø-240/120V UVWO Terminal Output Voltages
1. Place the voltage selector switch in the 1Ø 240/120
position as shown in Figure 24.
Figure 24. Voltage Selector Switch
1Ø-240/120V Position
2. Connect the load wires to the UVWO terminals as
shown in Figure 25.
Figure 25. UVWO Terminal Lugs
1Ø-240/120V Connection
3. Turn the voltage regulator knob ("Figure 20. Voltage
Regulator Knob" on page 24) clockwise to increase
voltage output, turn counterclockwise to decrease
voltage output. Use voltage regulator adjustment knob
whenever fine tuning of the output voltage is required.