DCA25SSIU4F 60 HZ GENERATOR• OPERATION MANUAL — REV. #4 (01/17/18) — PAGE 31
GENERATOR START-UP PROCEDURE (MANUAL)
4. The generator’s AC-voltmeter (Figure 38) will display
the generator’s output in
VOLTS. If the voltage is not
within the specified tolerance.
Figure 38. Voltmeter
5. Use the voltage adjustment control knob (Figure 39)
to increase or decrease the desired voltage.
Figure 39. Voltage Adjust Control Knob
6. The ammeter (Figure 40) will indicate
zero amps with
no load applied. When a load is applied, the ammeter
will indicate the amount of current that the load is
drawing from the generator.
Figure 40. Ammeter (No Load)
7. The engine oil pressure gauge (Figure 41) will indicate
the oil pressure of the engine. Under normal operating
conditions the oil pressure is approximately 35 to 65
psi. (193~586 kPa).
Figure 41. Oil Pressure Gauge
8. The
coolant temperature gauge (Figure 42) will
indicate the coolant temperature. Under normal
operating conditions the coolant temperature should
be between 180°~225°F (75°~95°C) (
Green Zone).
PSI
OIL PRESS
0
25
50
75
100
Figure 42. Coolant Temperature Gauge
9. The
tachometer gauge (Figure 43) will indicate the
speed of the engine when the generator is operating.
Under normal operating conditions this speed is
approximately 1800 RPM’s.
Figure 43. Engine Tachometer Gauge
10. Place the
main, GFCI, and aux. circuit breakers in the
ON position (Figure 44).
Figure 44. Main, Aux. and GFCI
Circuit Breakers (ON)
11. Observe the generator’s ammeter (Figure 45) and
verify it reads the anticipated amount of current with
respect to the load. The ammeter will only display a
current reading if a load is in use.
Figure 45. Ammeter (Load)
12. The generator will run until manually stopped or an
abnormal condition occurs.
°F
WATER TEMP
100
140
180
220
260
RPMX10
SPEED
0
120
150
180
210
60