PAGE 32 — DCA25SSIU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #4 (01/17/18)
GENERATOR START-UP PROCEDURE (AUTO MODE)
STARTING (AUTO MODE)
DANGER
Before connecting this generator to any
building’s electrical system, a
licensed
electrician must install an isolation
(transfer) switch. Serious damage to
the building’s electrical system may occur
without this transfer switch.
CAUTION
When connecting the generator to a isolation (transfer)
switch,
ALWAYS have power applied to the generator’s
internal battery charger. This will ensure that the engine
will not fail due to a dead battery.
WARNING
When running the generator in the
AUTO mode,
remember the generator can start up at any time without
warning.
NEVER attempt to perform any maintenance
when the generator is in the auto mode.
CAUTION
The engine speed switch
must be set to the “High”
position when running in the
auto-start mode. Failing
to set the switch in the proper position can result in
damage to your generator when it turns on.
NOTICE
When the generator is set in the
AUTO mode, the
generator will
automatically start in the event of
commercial power falling below a prescribed level
by means of a contact closure that is generated
automatically by a transfer switch.
NOTICE
When the
Auto Off/Reset Manual
switch is placed
in the
AUTO position, the engine glow plugs will be
warmed and the engine will start automatically.
When starting generator in
AUTO mode use the “Manual
Start-up” procedure except where noted (see below).
1. Perform steps 1 through 5 in the Before Starting section
as outlined in the Manual Starting Procedure.
2. Place the
Auto Off/Reset Manual Switch (Figure 46)
in the
AUTO position.
Figure 46.
Auto Off/Reset Manual
Switch (AUTO)
3. Continue operating the generator as outlined in the
Manual Start-up procedure (start at step 3).