background image

500kW Containerized

Diesel Generator Set

APPLICATION DATA

All ratings tested per MIL-STD-705 as applicable.

Generator protection for overload and short circuit.

Generator is designed and built within NEMA, IEEE and
ANSI standards for temperature rise.

PMG exciter for superior regulation and response.

Three phase sensing on regulator.

Skewed rotor for smooth voltage wave form.

.

Optional - Vacuum impregnated epoxy varnish, fungus
resistant per MIL-I-24092.

Alternator Features

Engine Specifications

Manufacturer/Model

Cummins / QSX15-G9

Engine Type

4-cycle, Turbocharged,

Air to Water Aftercooled

Cylinder Arrangement

6 In-line

Displacement

912 in

3

 (15 L)

Bore

5.39 in. (137 mm)

Stroke

6.65 in. (169 mm)

Compression Ratio

17 : 1

Piston Speed (60Hz)

1995 ft./min (10.1 m/sec)

Bearing Main:  Number

7

Bearing Main:  Type

Replaceable, Precision

Cylinder Block

Cast iron with wet, replaceable

cylinder liners

Cylinder Head Material

Cast iron

Crankshaft Material

Forged steel

Brake Mean Effective Pressure (BMEP)

360 psi (2482 kPa)

Rated RPM (60 Hz)

1800 RPM

Max. Power At Rated RPM (without fan)

755 hp (563 kW)

Governor: Type

Electronic

Frequency Regulation: Steady State

± 0.5%

Air Cleaner Type - All Models

Dry, Dual Element

Engine Electrical System

Battery Charging Alternator Ground Type

Negative

Volts

24 VDC

Ampere Rating

70A

Starter Motor Rated Voltage

24 VDC

Minimum Recommended Battery for

 0 °C / Cold Cranking Performance

1425 Ah

Alternator Specifications

Make

Marathon Magna Max

Type

4-Pole, Rotating Field

Number of Leads

10 or 12

Generator Type

 Rotating Field; PMG

Voltage Regulator

Solid State, Digital, Model DVR2000

Insulation

NEMA MG1-1.66

Material

Class H

Temperature Rise

105

o

C / 130

o

C

Bearing:  Number, Type

Single, Sealed

Coupling

Flexible Disk

Amortisseur Windings

Full

Excitation

Voltage Regulated, Brushless

Voltage Regulation (no load to full load)

0.25%

One Step Load Acceptance
% of rating per NFPA-110

100

Generator Efficiency at Full Load

93%

Phase Sequence

ABC (L1, L2, L3)

L-L Harmonic Max Total

5.0%

L-L Harmonic Max Single

3.0%

Amperage

Voltage

Phase

Power

Factor

Continuous Amperes

Standby

Prime

120/208 Volt

3

0.8

1910

1848

277/480 Volt

3

0.8

827

800

The EGC500C Sound Attenuated Generator is
configured for standard 60 Hz, 208V or 480V output.
Special voltage outputs are available (special
order)

.

Derating

Derating Factors (60 Hz)

Altitude

Ambient Temperature

The engine may be operated

up to 3000 ft. (915 m) altitude

without derating at 1800 rpm.

>3000 ft. =

1.8% per 1000 ft.

(300 m)

+10% per 10°C (18°F)

EGC500C  Rev 0

Summary of Contents for EGC-500C

Page 1: ...ulator Electronic automatic voltage regulator provides precise regulation Separate three phase excitation for fast recovery from block loads and motor starting Full Load Acceptance Accepts100 ofstandbynameplateratinginonestep incompliance with NFPA para 5 13 2 6 Generator Control Panel Basler vibration isolated controller Manual or remote engine start stop RS485 Modbus communication support Safety...

Page 2: ...r Cleaner Type All Models Dry Dual Element Engine Electrical System Battery Charging Alternator Ground Type Negative Volts 24 VDC Ampere Rating 70A Starter Motor Rated Voltage 24 VDC Minimum Recommended Battery for 0 C Cold Cranking Performance 1425 Ah Alternator Specifications Make Marathon Magna Max Type 4 Pole Rotating Field Number of Leads 10 or 12 Generator Type Rotating Field PMG Voltage Reg...

Page 3: ...ne RPM Engine run time Generator voltage Generator current Generator frequency Oil pressure Battery voltage Fuel level measurements Running Hour Meter Coolant temperature Generator under over voltage alarm shutdown Generator under over frequency alarm shutdown Over Current alarm shutdown Warm up and cooling functions Maintenance timer Digital Controller Features Cooling System Exhaust Manifold Typ...

Page 4: ...s approximate Wet weight does not include fuel Generator Set Genset to Genset Paralleling Control System Base Load to Utility Paralleling Control System Custom Outlet Panels Rotary Voltage Selector Switch High Wye Low Wye Voltages Auxiliary Oil Reservoir with Level Control 10 gallon Centrifugal Oil Filter System Oil Pan Heater with Thermostat Alternator Strip Heater AC Battery Charger with Shore P...