background image

500kW Containerized

Diesel Generator Set

Lubrication System

Type

Full Pressure System

Oil Filters

Spin-on, Full Flow

Oil Pan Capacity

22 gal. (83.0 L)

Oil Capacity with Filters

24 gal. (91.0 L)

Oil Pressure at Rated Speed (minimum)

20 psi (138 kPa)

Exhaust System

Exhaust Temperature at Rated kW

875 

o

F (468 

o

C)

Exhaust Flow at Rated kW

3200 cfm (90.6 m

3

/min)

Silencer Type

Critical

Maximum Allowable Backpressure (standby)

40.2 in/wc (10 kPa)

Exhaust Outlet Size at hook-up

5.0 in. (127 mm)

DGC-2020 Digital Genset Controller

Local and Remote Generator Control

Automatic and manual starting and stopping

Engine and Generator Protection

Programmable Analog Engine Senders

ECU Communications via SAE J1939

16 Programmable Contact Inputs

Programmable Logic

Automatic Transfer Switch Control (Mains Failure)

Integrated RS485

Auto Synchronizing

Event recording

Monitoring

Engine RPM

Engine run time

Generator voltage

Generator current

Generator frequency

Oil pressure

Battery voltage

Fuel level measurements

Running Hour Meter

Coolant temperature

Generator under/over voltage alarm/shutdown

Generator under/over frequency alarm/shutdown

Over Current alarm/shutdown

Warm up and cooling functions

Maintenance timer

Digital Controller Features

Cooling System

Exhaust Manifold Type

Dry

Radiator Design

Standard horizontal discharge

Coolant Capacity - Engine

6.3 gal. (24 L)

Water Pump Design/Type

Belt Driven, Centrifugal

Coolant Flow

87 gal/min (329 L/min)

Heat Rejection to Coolant

7830 BTU/min (138 kW)

Minimum Pressure Cap

10 psi (70 kPa)

Thermostat Range

180-200 °F (82-93 °C)

Fuel System

Recommended Fuel

ASTM-D975-No.1 or No. 2-D

Fuel Pump Maximum Lift

 6.0 ft. (1.8 m)

Filter Micron Size - 98% Efficiency

2

Total Fuel Flow

112 gal./hr. (424 L/Hr.)

Fuel Tank Capacity

800 gal (3028 L)

Fuel Consumption - gal/hr (L/hr)

Diesel Fuel @ % of Load

Standby

Prime

  25%

11.6 (43.9)

9.9 (37.4)

  50%

18.8 (71.1)

17.2 (65.3)

  75%

25.7 (97.2)

23.9 (90.5)

  100%

34.4 (130.2)

31.1 (117.8)

EGC500C  Rev 0

Summary of Contents for EGC-500C

Page 1: ...ulator Electronic automatic voltage regulator provides precise regulation Separate three phase excitation for fast recovery from block loads and motor starting Full Load Acceptance Accepts100 ofstandbynameplateratinginonestep incompliance with NFPA para 5 13 2 6 Generator Control Panel Basler vibration isolated controller Manual or remote engine start stop RS485 Modbus communication support Safety...

Page 2: ...r Cleaner Type All Models Dry Dual Element Engine Electrical System Battery Charging Alternator Ground Type Negative Volts 24 VDC Ampere Rating 70A Starter Motor Rated Voltage 24 VDC Minimum Recommended Battery for 0 C Cold Cranking Performance 1425 Ah Alternator Specifications Make Marathon Magna Max Type 4 Pole Rotating Field Number of Leads 10 or 12 Generator Type Rotating Field PMG Voltage Reg...

Page 3: ...ne RPM Engine run time Generator voltage Generator current Generator frequency Oil pressure Battery voltage Fuel level measurements Running Hour Meter Coolant temperature Generator under over voltage alarm shutdown Generator under over frequency alarm shutdown Over Current alarm shutdown Warm up and cooling functions Maintenance timer Digital Controller Features Cooling System Exhaust Manifold Typ...

Page 4: ...s approximate Wet weight does not include fuel Generator Set Genset to Genset Paralleling Control System Base Load to Utility Paralleling Control System Custom Outlet Panels Rotary Voltage Selector Switch High Wye Low Wye Voltages Auxiliary Oil Reservoir with Level Control 10 gallon Centrifugal Oil Filter System Oil Pan Heater with Thermostat Alternator Strip Heater AC Battery Charger with Shore P...

Reviews: