DCA-300SSK SERIES — PARTS AND OPERATION MANUAL (STD)— REV. #4 (03/27/06) — PAGE 37
DCA-300SSK SERIES — GEN. START-UP PROCEDURE (MANUAL)
Figure 42. Engine Enclosure Doors
Steps 1 thru 20 are referenced
for Engine Operating Panel S/N
3701673 and below. See Figure
40 below. This unit has an
igni-
tion
switch
and a
throttle
handle
.
NOTE
Figure 40. Engine Operating Panel
S/N 3701673 and Below
1. Place the
main, G.F.C.I.
and
aux.
circuit breakers (Figure 42)
in the “
OFF
” position prior to starting the engine.
Figure 42. Main, Aux. and GFCI
Circuit Breakers (OFF)
The engine's exhaust contains harmful emissions.
ALWAYS have adequate ventilation when operating
.
Direct exhaust away from nearby personnel.
CAUTION - LETHAL EXHAUST HAZARD
NEVER!
manually start the engine with the
main
,
GFCI
or
auxiliary
circuit breakers in the
ON
(closed) position.
WARNING - STARTING THE GENERATOR
2. Make sure the the
voltage change-over board
has
been configured for the desired output voltage.
3. Connect the load to the
UVWO
terminals or
auxiliary
receptacles
as shown in Figure 12. These load
connection points can be found on the output terminal
panel. To gain access to the UVWO terminals or other
power receptacles, unlock the access cover and lift the
door.
4. Tighten terminal nuts securely to prevent load wires from
slipping out
5. Close all engine enclosure doors (Figure 42).
BEFORE STARTING (
S/N 3701673 and below)