Outdoor Installation
Install the generator in a location where it will not be exposed
to rain or sunshine. Make sure the generator is on secure
level ground so it cannot slide or shift around. Also install
the generator so the exhaust will not be discharged in the
direction of nearby homes.
The installation site must be relatively free from moisture
and dust. All electrical equipment should be protected from
excessive moisture. Failure to do will result in deterioration
of the insulation and will result in short circuits and grounding.
Foreign materials such as dust, sand, lint and abrasive
materials have a tendency to cause excessive wear to the
engine and alternator parts.
CAUTION :
Pay close attention to ventilation when
operating the generator inside tunnels and
caves. The engine exhaust contains
noxious elements. Engine exhaust must
be routed to a ventilated area.
Indoor Installation
Exhaust gases from diesel engines are extremely poisonous.
Whenever an engine is installed indoors the exhaust fumes
must be vented to the outside. The engine should be installed
at least two feet from any outside wall. Using an exhaust
pipe which is too long or too small can cause excessive
back pressure which will cause the engine to heat
excessively and possibly burn the valves.
CAUTION
:
An electric shock may happen when
vibrators are used. Pay close attention to
handling when operating vibrators and
always use rubber boots and gloves to
insulate the body from electrical shock.
Generator Grounding
To guard against electrical shock and possible damage to
the equipment, it is important to provide a good
EARTH
ground.
Article 250 (Grounding) of the National Electrical Code (NEC)
provides guide lines for proper grounding and specifies that
the cable ground shall be connected to the grounding system
of the building as close to the point of cable entry as
practical.
NEC articles 25064(b) a and 250-66 set the following
grounding requirements:
1. Use one of the following wire types to connect the
generator to earth ground.
a. Copper - 10 AWG (5.3 mm
2
) or larger.
b. Aluminum - 8 AWG (8.4 mm
2
) or larger.
2. When grounding the generator (Figure 32) connect the
ground cable between the lock washer and the nut on
the generator and tighten the nut fully. Connect the other
end of the ground cable to earth ground.
3. NEC article 250-52(c) specifies that the earth ground
rod should be buried a minimum of 8 ft. into the ground.
DCA-60SSAI — INSTALLATION
NOTE
When connecting the generator to any buildings
electrical system
ALWAYS
consult with a licensed
electrician.
Summary of Contents for WHISPERWATT DCA-60SSAI
Page 2: ...PAGE 2 DCA 60SSAI PARTS AND OPERATION MANUAL FINAL COPY 09 15 01 ...
Page 22: ...PAGE 22 DCA 60SSAI PARTS AND OPERATION MANUAL FINAL COPY 09 15 01 DCA 60SSAI GENERATOR DECALS ...
Page 27: ...DCA 60SSAI PARTS AND OPERATION MANUAL FINAL COPY 09 15 01 PAGE 27 NOTE PAGE ...
Page 51: ...DCA 60SSAI PARTS AND OPERATION MANUAL FINAL COPY 09 15 01 PAGE 51 NOTE PAGE ...
Page 61: ...DCA 60SSAI PARTS AND OPERATION MANUAL FINAL COPY 09 15 01 PAGE 61 NOTE PAGE ...
Page 151: ...DCA 60SSAI PARTS AND OPERATION MANUAL FINAL COPY 09 15 01 PAGE 151 NOTE PAGE ...