PAGE 36 — DCA125SSIU 50 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #0 (12/22/08)
GENERATOR START-UP PROCEDURE (AUTO MODE)
STARTING (AUTO MODE)
DANGER
Before connecting this generator to any
building’s electrical system, a
licensed
electrician
must install an
isolation
(transfer) switch.
Serious damage to
the building’s electrical system may occur without this
transfer switch.
CAUTION
When connecting the generator to a isolation (transfer)
switch,
ALWAYS
have power applied to the generator’s
internal battery charger. This will ensure that the engine
will not fail due to a dead battery.
NOTICE
When the generator is set in the
AUTO
mode, the
generator will
automatically start
in the event of
commercial power falling below a prescribed level
by means of a contact closure that is generated
automatically by a transfer switch.
WARNING
When running the generator in the
AUTO
mode,
remember the generator can start up at any time without
warning.
NEVER
attempt to perform any maintenance
when the generator is in the auto mode.
CAUTION
The engine speed switch
must
be set to the “High”
position when running in the
auto-start
mode. Failing
to set the switch in the proper position can result in
damage to your generator when it turns on.
NOTICE
When the MPEC control switch is placed in the
AUTO
position, the engine glow plugs will be warmed and the
engine will start automatically.
When starting generator in
AUTO
mode use the “Manual
Start-up” procedure except where noted (see below).
Perform steps 1 through 5 in the Before Starting section
1.
as outlined in the Manual Starting Procedure.
Place the
2.
engine speed switch
(Figure 51) in the
HIGH
position
Engine Speed Switch (High)
Figure 51.
Place the
3.
MPEC Control Switch
(Figure 52) in the
AUTO
position.
MPEC Control Switch (AUTO)
Figure 52.
Continue operating the generator as outlined in the
4.
Manual Start-up procedure (start at step 5).
Summary of Contents for WHISPERWATT DCA125SSIU
Page 19: ...DCA125SSIU 50 HZ GENERATOR OPERATION AND PARTS MANUAL REV 0 12 22 08 PAGE 19 NOTES ...
Page 54: ...PAGE 54 DCA125SSIU 50 HZ GENERATOR OPERATION AND PARTS MANUAL REV 0 12 22 08 GENERATOR ASSY ...
Page 56: ...PAGE 56 DCA125SSIU 50 HZ GENERATOR OPERATION AND PARTS MANUAL REV 0 12 22 08 CONTROL BOX ASSY ...
Page 58: ...PAGE 58 DCA125SSIU 50 HZ GENERATOR OPERATION AND PARTS MANUAL REV 0 12 22 08 CONTROL BOX ASSY ...
Page 60: ...PAGE 60 DCA125SSIU 50 HZ GENERATOR OPERATION AND PARTS MANUAL REV 0 12 22 08 CONTROL BOX ASSY ...
Page 68: ...PAGE 68 DCA125SSIU 50 HZ GENERATOR OPERATION AND PARTS MANUAL REV 0 12 22 08 BATTERY ASSY ...
Page 70: ...PAGE 70 DCA125SSIU 50 HZ GENERATOR OPERATION AND PARTS MANUAL REV 0 12 22 08 MUFFLER ASSY ...
Page 72: ...PAGE 72 DCA125SSIU 50 HZ GENERATOR OPERATION AND PARTS MANUAL REV 0 12 22 08 FUEL TANK ASSY ...
Page 87: ...DCA125SSIU 50 HZ GENERATOR OPERATION AND PARTS MANUAL REV 0 12 22 08 PAGE 87 NOTES ...