DCa180SSI/DCa180SSIu 60 hz gen/ • operaTIon anD parTS manual — rev. #1 (08/02/10) — page 29
OUtpUt terMinaL paneL cOnnectiOns
3Ø-480v uvWo Terminal output voltages
1. Jumper the voltage change-over board for 480V
operation as shown in Figure 24. This configuration
uses 6 jumper plates in 3 different positions. Remember
there are 2 jumper plates at every position. Every
jumper plate
must
be used.
Figure 24. Voltage Change-Over Board 480V
Configuration
2. Connect the load wires to the UVWO terminals as
shown in Figure 25.
Figure 25. UVWO Terminal Lugs 3Ø-480V
Connections
NOTICE
alWaYS
make sure that the connections to the UVWO
terminals are
secure
and
tight
. The possibility of arcing
exists, that could cause a fire.
1Ø-480v uvWo Terminal output voltages
1. Make sure the voltage change-over board is jumpered
for 480V operation as shown in Figure 24.
2. Connect the load wires to the UVWO terminals as
shown in Figure 26.
Figure 26. UVWO Terminal Lugs 1Ø-480V
Connections
1Ø-277v uvWo Terminal output voltages
1. Make sure the voltage change-over board is jumpered
for 480V operation as shown in Figure 24.
2. Connect the load wires to the UVWO terminals as
shown in Figure 27.
Figure 27. UVWO Terminal Lugs 1Ø-277V
Connections
Summary of Contents for Whisperwatt DCA180SSI
Page 19: ...DCA180SSI dca180ssiu 60 hz Gen operation and parts manual rev 1 08 02 10 page 19 Notes ...
Page 53: ...DCA180SSI dca180ssiu 60 hz Gen operation and parts manual rev 1 08 02 10 page 53 notes ...
Page 80: ...page 80 DCA180SSI dca180ssiu 60 hz Gen operation and parts manual rev 1 08 02 10 Muffler Assy ...
Page 105: ...DCA180SSI dca180ssiu 60 hz Gen operation and parts manual rev 1 08 02 10 page 105 notes ...