DCa180SSI/DCa180SSIu 60 hz gen/ • operaTIon anD parTS manual — rev. #1 (08/02/10) — page 33
of the battery fluid is 1.28 (at 68° F). If the specific gravity
should fall to 1.245 or lower, it indicates that the battery is
dead and needs to be recharged or replaced.
Before charging the battery with an external electric source,
be sure to disconnect the battery cables.
Battery Cable Installation
alWaYS
be sure the battery cables (Figure 35) are
properly connected to the battery terminals as shown below.
The
red cable
is connected to the positive terminal of the
battery, and the
black cable
is connected to the negative
terminal of the battery.
Figure 35. Battery Connections
When connecting battery do the following:
1.
never
connect the battery cables to the battery
terminals when the
mpeC Control Switch
is in either
the
manual
position.
alWaYS
make sure that the
mpeC Control Switch
is in the
oFF/reSeT
position
when connecting the battery.
2. Place a small amount of battery terminal treatment
compound around both battery terminals. This will
ensure a good connection and will help prevent
corrosion around the battery terminals.
CauTIon
alWaYS
disconnect the negative terminal
FIrST
and
reconnect negative terminal
laST
.
NOTICE
If the battery cable is connected incorrectly, electrical
damage to the generator will occur. Pay close attention to
the polarity of the battery when connecting the battery.
CauTIon
Inadequate battery connections may cause poor
starting of the generator, and create other malfunctions.
alTernaTor
The polarity of the alternator is negative grounding type.
When an inverted circuit connection takes place, the
circuit will be in short circuit instantaneously resulting the
alternator failure.
Do noT
put water directly on the alternator. Entry of water
into the alternator can cause corrosion and damage the
alternator.
WIrIng
Inspect the entire generator for bad or worn electrical wiring
or connections. If any wiring or connections are exposed
(insulation missing) replace wiring immediately.
pIpIng anD hoSe ConneCTIon
Inspect all piping, oil hose, and fuel hose connections for
wear and tightness. Tighten all hose clamps and check
hoses for leaks.
If any hose (
fuel or oil
) lines are defective replace them
immediately.
inspectiOn/setUp
Summary of Contents for Whisperwatt DCA180SSI
Page 19: ...DCA180SSI dca180ssiu 60 hz Gen operation and parts manual rev 1 08 02 10 page 19 Notes ...
Page 53: ...DCA180SSI dca180ssiu 60 hz Gen operation and parts manual rev 1 08 02 10 page 53 notes ...
Page 80: ...page 80 DCA180SSI dca180ssiu 60 hz Gen operation and parts manual rev 1 08 02 10 Muffler Assy ...
Page 105: ...DCA180SSI dca180ssiu 60 hz Gen operation and parts manual rev 1 08 02 10 page 105 notes ...