PAGE 24 — DCA20SPXU4F • OPERATION MANUAL — REV. #3 (09/18/19)
OUTPUT TERMINAL PANEL CONNECTIONS
CIRCUIT BREAKERS
To protect the generator from an overload, a 3-pole, 90
amp, main circuit breaker is provided to protect the
U,O,
and V Output Terminals
from overload. In addition two
single-pole, 20 amp
GFCI
circuit breakers are provided to
protect the GFCI receptacles from overload. Two 50 amp
load
circuit breakers have also been provided to protect the
auxiliary receptacles from overload. Make sure to switch
ALL
circuit breakers to the
OFF
position prior to starting
the engine.
LUBRICATION OIL
Fill the engine crankcase with lubricating oil through the
filler hole, but
DO NOT
overfill. Make sure the generator is
level and verify that the oil level is maintained between the
two notches (Figure 16) on the dipstick. See Table 7 for
proper selection of engine oil.
Figure 16. Engine Oil Dipstick
When checking the engine oil, be sure to check if the oil is
clean. If the oil is not clean, drain the oil by removing the
oil drain plug, and refill with the specified amount of oil as
outlined in the
Isuzu Engine Owner’s Manual
. Oil should
be warm before draining.
Delo® engine oil is the recommended engine oil for this
generator. When replacing engine oil please refill using
Delo® 400 LE SAE 15W-40 (API CJ-4) engine oil.
Table 7. Recommended Motor Oil
FUEL CHECK
Refilling the Fuel System
This generator has an internal fuel tank (Figure 17) located
inside the enclosure and may also be equipped with a trailer
mounted fuel tank.
ALWAYS
fill the fuel tank with clean fresh
#2 diesel fuel. DO NOT
fill the fuel tank beyond its capacity.
Pay attention to the fuel tank capacity when replenishing
fuel. The fuel tank cap must be closed tightly after filling.
Handle fuel in a safety container. If the container does not
have a spout, use a funnel. Wipe up any spilled fuel
immediately.
Figure 17. Fuel Tank
DANGER
Fuel spillage on a
hot
engine can cause
a
fire
or
explosion
. If fuel spillage occurs,
wipe up the spilled fuel completely to
prevent fire hazards.
NEVER
smoke
around or near the generator.
CAUTION
ONLY properly trained personnel
who have read
and understand this section should refill the fuel tank
system.
INTERNAL
FUEL TANK
FUEL
CAP
Summary of Contents for WHISPERWATT DCA20SPXU4F
Page 2: ...PAGE 2 DCA20SPXU4F OPERATION MANUAL REV 3 09 18 19 PROPOSITION 65 WARNING ...
Page 41: ...DCA20SPXU4F OPERATION MANUAL REV 3 09 18 19 PAGE 41 GENERATOR WIRING DIAGRAM ...
Page 42: ...PAGE 42 DCA20SPXU4F OPERATION MANUAL REV 3 09 18 19 ENGINE WIRING DIAGRAM ...
Page 45: ...DCA20SPXU4F OPERATION MANUAL REV 3 09 18 19 PAGE 45 NOTES ...