DCA250SSI
WhisperWatt
TM
Generator
Standard Features
■
Heavy duty, turbocharged, direct injection, air to air
intercooled diesel engine
provides maximum reliability.
■
Brushless alternator
reduces service and maintenance
requirements and meets temperature rise standards for
Class F insulation systems.
■
Open delta alternator design
provides virtually
unlimited excitation for maximum motor starting capability.
■
Automatic voltage regulator
(AVR) provides precise
regulation.
■
Electronic governor system
maintains frequency to
±0.25%.
■
Full load acceptance
of standby nameplate rating in
one step (NFPA 110, para 5-13.2.6).
■
Sound attenuated, weather resistant, steel housing
provides operation at 68 dB(A) at 23 feet. Fully lockable
enclosure allows safe unattended operation.
■
Internal fuel tank
with direct reading fuel gauges are
standard.
■
Fuel / water separator
removes condensation from fuel
for extended engine life.
■
E-Coat primer
with polyurethane enamel finish coat.
■
Emergency stop switch
WhisperWatt
TM
250
■
Complete engine analog instrumentation
includes
DC ammeter, oil pressure gauge, water temp. gauge, fuel
level gauge, tachometer/hour meter, preheat indicator,
manual engine speed control, and emergency shutdown
monitors.
■
Complete generator analog instrumentation
includes
voltage regulator control, ammeter phase selector switch,
voltmeter phase selector switch, AC voltmeter, AC
ammeter, frequency meter, panel light, and circuit breaker.
■
Automatic safety shutdown system
monitors the
water temperature, engine oil pressure, overspeed, and
overcrank. Warning lights indicate abnormal conditions.
■
Low coolant level shutdown system
provides
protection from critically low coolant levels. Includes
control panel warning light.
■
Auto start/stop control
allows generator to start
automatically in the event of a commercial power failure.
■
Complete power panel.
Fully covered; three-phase
terminals and single phase receptacles allow fast and
convenient hookup for most applications including
temporary power boxes, tools and lighting equipment.
All are NEMA standard.
■
EPA emissions certified
- Tier 3 emissions compliant.
Prime Rating:
200 kW (250 kVA)
Standby Rating:
220 kW (275 kVA)
60 Hertz
DCA250SSI Rev 0
250