Generator Specifications

Design

Revolving field, Self-ventilated

Drip-proof, Single bearing

No. of Poles

4-pole

Excitation

Brushless with AVR

Standby Output

220 kW (275 kVA)

Prime Output

200 kW (250 kVA)

Generator RPM

1800

Voltage — 3Ø

208, 220, 240, 416, 440, 480V Reconnectable

Voltage — 1Ø

120, 127, 139, 240, 254, 277V Adjustable

Armature Connection

Star with neutral

Voltage Regulation

(No load to full load)

±0.5%

Power Factor

0.8

Frequency

60 Hz

Frequency Regulation:

No Load to Full Load

Isochronous under varying loads from

no load to 100% rated load

Frequency Regulation:

Steady State

±0.25% of mean value for constant loads

from no load to full load

Insulation

Class F

Sound Level dB(A)

Full load at 23 ft

68

Engine  Specifications

Make/Model

Isuzu / 6UZ1X

Emissions

EPA Tier 3 Certified

Starting System

Electric

Design

4-Cycle, Water cooled, Direct injection,

Turbocharged, Air cooled

Displacement

9839 cc

No. cylinders

6

Bore x Stroke (mm)

120 x 145

Gross Engine Power Output

348 hp (259 kW)

BMEP

252 psi (1735 kPa)

Piston Speed

1713 ft/min (8.7 m/s)

Compression Ratio

17.5 : 1

Engine Speed

1800 rpm

Overspeed Limit

2070 rpm

Oil capacity gallons (liters)

10.8 gal (41.0 L)

Battery

12V 150 Ah x 2

Fuel  System

Recommended Fuel

ASTM-D975-No.1 or No. 2-D

Maximum Fuel Flow (per hour)

98.8 gal (347 L)

Maximum Inlet Restriction (Hg)

8.86 in. (225 mm)

Fuel Tank Capacity

121 gal (460 L)

Fuel Consumption

full load gph (lph)

14.7 (55.8)

75% load gph (lph)

10.9 (41.2)

50% load gph (lph)

7.5 (28.5)

25% load gph (lph)

4.4 (16.6)

Amperage

Rated Voltage

Maximum Amps

1Ø 120 Volt

555.5 Amps (4 wire)

1Ø 240 Volt

277.7 Amps (4 wire)

3Ø 240 Volt

601 Amps

3Ø 480 Volt

301 Amps

Main Line Circuit Breaker Rating

800 Amps

Over Current Relay Trip Set Point

301 Amps

Cooling System

Fan Load

5.6 hp (4.2 kW)

Coolant Capacity (with radiator)

14.3 gal (54.0 L)

Coolant Flow Rate (per minute)

56.8 gal. (215 L)

Heat Rejection to Coolant (per minute)

7489 Btu (7.90 MJ)

Heat Radiated to Room

2095 Btu (2.21 MJ)

Maximum Coolant Friction Head

8.1 psi (56.0 kPa)

Maximum Coolant Static Head

29.5 ft (9.0 m)

Ambient Temperature Rating

104°F (40°C)

Air

Combustion Air

498 cfm (14.1 m

3

/min)

Maximum Air Cleaner Restriction

13.6 in H

2

0 (3.4 kPa)

Alternator Cooling Air

1459 cfm (41.3 m

3

/min)

Radiator Cooling Air

8404 cfm (238 m

3

/min)

Exhaust System

Gas Flow (full load)

1261 cfm (35.7 m

3

/min)

Gas Temperature

1004°F (540°C)

Maximum Back Pressure

53.2 in. H

2

0 (13.3 kPa)

Generator is not intended for use in enclosed areas or where free flow of air is restricted.

Backfeed to a utility system can cause electrocution and/or property damage.  Do not
connect to any building’s electrical system except through an approved device.

                         

Specifications are subject to change without notice.

DCA250SSI  Rev 0

Warranty*

Isuzu Engine

12 months from date of purchase with unlimited hours or 24 months
from date of purchase with 2000 hours (whichever comes first).

Generator

24 months from date of purchase or 2000 hours (whichever occurs
first).

Trailer

12 months excluding normal wear items.

*Refer to the express written, one-year limited warranty sheet for additional
information.

Summary of Contents for WhisperWatt DCA250SSI

Page 1: ...M 250 Complete engine analog instrumentation includes DC ammeter oil pressure gauge water temp gauge fuel level gauge tachometer hour meter preheat indicator manual engine speed control and emergency shutdown monitors Complete generator analog instrumentation includes voltage regulator control ammeter phase selector switch voltmeter phase selector switch AC voltmeter AC ammeter frequency meter pan...

Page 2: ...lph 10 9 41 2 50 load gph lph 7 5 28 5 25 load gph lph 4 4 16 6 Amperage Rated Voltage Maximum Amps 1Ø 120 Volt 555 5 Amps 4 wire 1Ø 240 Volt 277 7 Amps 4 wire 3Ø 240 Volt 601 Amps 3Ø 480 Volt 301 Amps Main Line Circuit Breaker Rating 800 Amps Over Current Relay Trip Set Point 301 Amps Cooling System Fan Load 5 6 hp 4 2 kW Coolant Capacity with radiator 14 3 gal 54 0 L Coolant Flow Rate per minute...

Page 3: ...also available Optional Fuel Cell Features Trailer fuel tank a second fuel cell located in the trailer allows for extended run time Subbase fuel cells double wall Additional fuel cell for extended runtime operation Contains a leak sensor low fuel level switch and a secondary containment tank UL142 listed 12 hours of minimum run time 24 hours of minimum run time Optional Control Features Audible al...

Page 4: ...ER Rev 0 01 09 DCA250SSIC Manufactured by Denyo Co MQ POWER POST OFFICE BOX 6254 CARSON CA 90749 310 537 3700 800 883 2551 FAX 310 604 3831 E MAIL mqpower multiquip com WWW mqpower com Weight Dry Weight 8203 lbs 3720 kg Wet Weight 9305 lbs 4220 kg Max Lifting Point Capacity 14050 lbs 6373 kg ...

Reviews: