PAGE 32 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
GENERATOR OUTPUTS
GENERATOR OUTPUT VOLTAGES
A wide range of voltages are available to supply voltage for
many different applications. Voltages are selected by using
the
voltage change-over board
(Figure 20). To obtain
some of the voltages as listed in Table 9 (see below) will
require a fine adjustment using the
voltage regulator
(VR)
control knob
located on the control panel.
Voltage Change-Over Board
The
voltage change-over board
(Figure 20) is located on
the control box, behind the generator control panel. This
board has been provided for ease of voltage selection.
Figure 20. Voltage Change-Over Board
X
Y
Z
O
U
U
1
2
V
V
2
1
W
W
2
1
JUMPER
6 PLACES
1
2
3
4
5
6
CAUTION
NEVER
attempt to place jumper plates on the
voltage
change-over board
while the generator is in operation.
There exist the possibility of
electrocution, electrical
shock or burn, which can cause severe bodily harm
or even death!
Table 9. Voltages Available
UVWO Output
Terminal Lugs
Voltage Change-Over Board
3-Phase 240/139V Position
Voltage Change-Over Board
3-Phase 480/270V Position
3Ø
Line-Line
208V
220V
240V
416V
440V
480V
1Ø
Line-Neutral
120V
127V
139V
240V
254V
277V
Voltage Change-Over Board Single-Phase 240/120V Position
1Ø
Line-Neutral/
Line-Line
120V
Line-Neutral
N/A
N/A
240V
Line-Line
N/A
N/A
Maximum Amps
Table 10 shows the
maximum
amps the generator can
provide.
DO NOT
exceed the maximum amps as listed.
Table 10. Generator Maximum Amps
Rated Voltage
Maximum Amps
1Ø 120 Volt
666.7 X 2 amps (4 wire)
1Ø 240 Volt
333.3 amps (4 wire)
3Ø 240 Volt
722 amps
3Ø 480 Volt
360 amps
Main Line Circuit
Breaker Rating
800 amps