PAGE 16 — DCA45SSIU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #5 (02/28/20)
ENGINE/GENERATOR CONTROL PANEL
The definitions below describe the controls and functions
of the Engine/Generator Control Panel (Figure 4).
1.
ECU Controller with Gauge Unit Assembly
— This
assembly houses the various engine monitoring
gauges. These gauges indicate: oil pressure, water
temperature, charging voltmeter, fuel, and engine
speed RPM (tachometer).
A.
Oil Pressure Gauge
— During normal operation
this gauge should read approximately 50 psi
(345 kPa). When starting the generator the oil
pressure may read a little higher, but after the
engine warms up the oil pressure should return
to the correct pressure range.
B.
Water Temperature Gauge
— During normal
operation this gauge should indicate approximately
180°F (82°C).
C.
Charging Voltmeter Gauge
— During normal
operation this gauge should indicate minimum
14 VDC.
D.
Fuel Gauge
— Indicates amount of diesel fuel
available.
E.
Tachometer
— Indicates engine speed in RPM
for 60 Hz operation. This meter should indicate
1,800 rpm when the rated load is applied.
Figure 4. Engine/Generator Control Panel
Low Oil Pressure
High Temp
Over Crank
Over Speed
Engine
Started
Low
Fuel
ECU
Integrated Gauge Control
R
n/min
D
D
n/min
A
B
C
PSI
OIL PRESS
0
25
50
75
100
D
E
F
2
3
4
5
6
9
7
8
10
11
12
16
15
14
13
Low Oil Pressure
High Temp
Over Crank
Over Speed
Engine
Started
Low
Fuel
ECU
Integrated Gauge Control
R
n/min
D
D
n/min
1
F.
Warning LEDs
• Low Oil Pressure LED
— This LED will light when
the engine oil pressure drops to 14.2 psi. This
condition will cause the engine to shut down.
• High Temperature LED
— This LED will light
when the coolant temperature has reached
212°F (100°C). This condition will cause the
engine to shut down.
• Over Crank LED
— This LED will light when
the engine has attempted to start 3 times and
failed. The interval between the 3 start cycles
is approximately 10 seconds.
• Over Speed LED
— This LED will light when
the engine is running at an unsafe speed. This
condition will cause the engine to shut down.
• Engine Started LED
— This LED will light when
the engine has started and is operating correctly.
• Low Fuel LED
— When ON (lit) indicates that
20% fuel remains. Engine will shutdown with
5% fuel remaining.
2.
Panel Light Switch
— When activated will turn on the
control panel light.
3.
Panel Light
— For operation at night, the panel light
illuminates the control panel for ease of reading meters
and gauges. Make sure the panel light switch is in the
OFF
position when the light is not in use.