PAGE 22 — DCA45SSIU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #5 (02/28/20)
GENERATOR OUTPUTS
GENERATOR OUTPUT VOLTAGES
A wide range of voltages are available to supply voltage for
many different applications. Voltages are selected by using
the
voltage selector
switch
(Figure 12). To obtain some of
the voltages as listed in Table 7 (see below) will require a
fine adjustment using the
voltage regulator (VR) control
knob
located on the control panel.
Voltage Selector Switch
The voltage selector switch (Figure 12) is located above
the output terminal panel’s Hard Wire Hook-Up Panel. It
has been provided for ease of voltage selection..
Figure 12. Voltage Selector Switch
PRESS TO LOCK
3 PHASE
480/277
3 PHASE
240/139
1 PHASE
240/120
CAUTION
NEVER
change the position of the
voltage selector
switch
while the engine is running.
ALWAYS
place
the circuit breaker in the
OFF
position before selecting
voltage.
Table 7. Voltages Available
UVWO Output
Terminal Lugs
Voltage Selector Switch
3-Phase 240/139V Position
Voltage Selector Switch
3-Phase 480/270V Position
3Ø
Line-Line
208V
220V
240V
416V
440V
480V
1Ø Line-Neutral
120V
127V
139V
240V
254V
277V
Voltage Selector Switch Single-Phase 240/120V Position
1Ø Line-Neutral/
Line-Line
120V
Line-Neutral
N/A
N/A
240V
Line-Line
N/A
N/A
Maximum Amps
Table 8 shows the
maximum
amps the generator can
provide.
DO NOT
exceed the maximum amps as listed.
GFCI Receptacle Load Capability
The load capability of the GFCI receptacles is directly
related to the voltage being supplied at either the output
terminals or the three twist-lock auxiliary receptacles.
Figure 17, Table 9 and Table 10 show what amount of
current is available at the GFCI receptacles when the output
terminals and twist-lock receptacles are in use. Be careful
that your load does not exceed the available current
capability at the receptacles.
Table 8. Generator Maximum Amps
Rated Voltage
Maximum Amps
1Ø 120 volts
108 amps × 2 (zigzag)
1Ø 240 volts
108 amps (zigzag)
3Ø 240 volts
108 amps
3Ø 480 volts
54 amps
Main Line Circuit
Breaker Rating
110 amps
Table 9. 1Ø GFCI Receptacle Load Capacity
kW in Use
Twist Lock (CS6369)
Available Load
Current (Amps)
1Ø 240/120V
GFCI Duplex
5-20R 120V
26
0
24.8
5 amps/receptacle
23.6
10 amps/receptacle
22.4
15 amps/receptacle
21.2
20 amps/receptacle
Table 10. 3Ø Generator Maximum Amps
kVA in Use
(UVWO Terminals)
Available Load
Current (Amps)
3Ø 240/480V
GFCI Duplex
5-20R 120V
45
0 amps/receptacle
40.9
5 amps/receptacle
36.7
10 amps/receptacle
32.6
15 amps/receptacle
28.4
20 amps/receptacle