DCA45SSIU4F 60 HZ GENERATOR• OPERATION MANUAL — REV. #5 (02/28/20) — PAGE 25
OUTPUT TERMINAL PANEL CONNECTIONS
3Ø-480/277V UVWO Terminal Output Voltages
1. Place the voltage selector switch in the 3Ø 480/277
position as shown in Figure 22.
Figure 22. Voltage Selector Switch
3Ø-480/277V Position
2. Connect the load wires to the UVWO terminals as
shown in Figure 23.
Figure 23. UVWO Terminal Lugs 3Ø-480V
Connections
PRESS TO LOCK
3 PHASE
480/277
3 PHASE
240/139
1 PHASE
240/120
O
U
V
W
480V
BLACK
RED
BLUE
480V
277V
480V
277V
WHITE
GREEN
277V
GROUND CONNECTION
MUST
BE USED
AT ALL TIMES
NOTICE
ALWAYS
make sure that the connections to the UVWO
terminals are
secure
and
tight
. The possibility of arcing
exists, that could cause a fire.
1Ø-240/120V UVWO Terminal Output Voltages
1. Place the voltage selector switch in the 1Ø 240/120
position as shown in Figure 24.
Figure 24. Voltage Selector Switch
1Ø-240/120V Position
2. Connect the load wires to the UVWO terminals as
shown in Figure 25.
Figure 25. UVWO Terminal Lugs
1Ø-240/120V Connection
3. Turn the voltage regulator knob (Figure 20) clockwise
to increase voltage output, turn counterclockwise to
decrease voltage output. Use the voltage regulator
adjustment knob whenever fine tuning of the output
voltage is required.
PRESS TO LOCK
3 PHASE
480/277
3 PHASE
240/139
1 PHASE
240/120
O
U
V
W
BLACK
RED
BLUE
WHITE
GREEN
NOT USED
GROUND CONNECTION
MUST
BE USED
AT ALL TIMES
240V
120V
120V