9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
105
6385142/08 EN
ETOS
®
ED
To establish a connection, proceed as follows:
1. Connect the PC and device using an Ethernet cable (RJ45 plug) via the
ETH2.1 or ETH2.2 interface.
Figure 79: Establishing a connection via the ETH2.1 or ETH2.2 interface
2. Assign a unique IP address to the PC. This IP address must be in the
same subnet as the device (e.g. ETH2.1:
192.168.165.100
).
3. Enter the IP address of the visualization (e.g. ETH2.1:
http://192.168.165.1
; if SSL encryption is active, enter
https://192.168.165.1
) in the browser on the PC.
ð
The visualization is accessed.
ETOS® ED with display
You can use the ETH1.1 front interface or the optional ETH2.2 interface of
the CPU assembly to establish the connection to the visualization. To do
this, observe the following configuration example:
Interface
Configuration
Standard
ETH1.1
IP address: 192.168.165.1 (not adjustable)
PC
Automatic configuration via DHCP
Optional
ETH2.2
IP address: 192.0.1.230 (factory setting) [
Subnet mask: 255.255.255.0
PC
IP address: 192.0.1.100
Subnet mask: 255.255.255.0
Table 20: Interface configuration example