9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
146
6385142/08 EN
ETOS
®
ED
Column
Description
Modifiable
Setting range
PREFSTATICVAR
For a data point of class 0 (Static), you can define the fol-
lowing variation depending on the object group:
▪ BI: 1, 2
▪ BO: 2
▪ AI: 2, 4
▪ AO: 2
▪ CT: 1, 2, 5, 6
Yes
0...6
PREFEVENTVAR
For a data point of classes 1...3 (Event), you can define
the following variation depending on the object group:
▪ BI: 1, 2, 3
▪ BO: no value
▪ AI: 2, 4
▪ AO: no value
▪ CT: 1, 2, 5, 6
Yes
0...6
NAME
Data point designation.
No
-
Deadband
Threshold value for analog inputs. The data point is only
transferred again if the change of value is greater than the
threshold value.
▪ If you enter the value 0, no threshold value is active.
▪ If you do not enter any value, the device adopts the
threshold value defined by the device parameter. If no
device parameter is available for the threshold value,
no threshold value is active either.
Notice: The threshold value has the same unit as the data
point value. Take note of the list of data points.
Yes
0...32,768
Table 39: Configuring DNP3 data points
Figure 105: Configuring DNP3 data points
Proceed as follows to configure the data points:
1. Go to
Settings > Data point configuration
.