9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
151
6385142/08 EN
ETOS
®
ED
9.10.2 Linking digital outputs
You can link each event with a digital output. The device provides a maxi-
mum of 20 digital outputs for this purpose. When you link a digital output to
an event, the device issues a signal to this output if the event occurs. The
signal persists until the event stops. A parameter is available for each avail-
able digital output.
To forward input signals or control system commands, you need to link the
digital outputs or control system messages with the
Generic digital input
or
Generic SCADA command
events.
Settings
Parameters
Link outputs
Name
Value
Generic digital output 1
500
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
04.02.2020 11:14
Figure 110: Linking digital outputs
ü
The desired event number is known [
1. Go to
Settings > Parameters > System > Link outputs
.
2. Select the desired parameter.
3. Enter the desired event number.
4. Press the
Accept
button to save the modified parameter.
9.10.3 Linking control system messages
You can link each event with a control system message. The device pro-
vides 10 SCADA messages for this purpose. When you link a SCADA mes-
sage to an event, the device sets the data point to "On" when the event oc-
curs. When the event stops, the device sets the data point to "Off". A param-
eter is available for each available SCADA message.
To forward control system commands, you need to link the control system
messages to the
Generic digital input
or
Generic SCADA command
events.