If the measured value is higher than the upper limit (> or >>) or lower than
the lower limit (< or <<), the device transmits an event message.
I>>
I<
I
t
I>
I<<
t
V
t
E
H
Figure 157: Example of current monitoring with the limit value I> being exceeded
I>> Upper limit 2
I> Upper limit 1
I< Lower limit 1
I<< Lower limit 2
t
V
Delay time
t
E
Event duration
H Hysteresis
You can set the following parameters for each limit value:
▪ Relative/absolute limit value
▪ Limit value [A] or [kA]: Absolute limit value
▪ Limit value [%]: Limit value relative to the rated current of current trans-
former. With current measurements via the analog input, the value is rela-
tive to the maximum value of the analog input (e.g. 100% = 20 mA).
▪ Hysteresis limit value
▪ Delay time limit value
▪ Behavior limit value (only for devices with voltage regulation)