9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
242
6385142/08 EN
ETOS
®
ED
Behavior
You can use this parameter to set the behavior of the device when the event
message is issued. You can select the following options:
Setting
Behavior
Off
The limit value is not monitored.
Auto blocking
Automatic regulation is blocked.
You can continue to perform tap-change operations in
manual mode.
Auto/manual blocking
Automatic regulation is blocked.
You
cannot
perform tap-change operations in manual
mode.
Table 79: Behavior when an event message is issued
9.22.9 Temperature monitoring
You can set different limit values for every measured/calculated temperature
. If the measured temperature is greater than limit value > or >>, the device
triggers an event message. If the measured temperature is less than limit
value < or <<, the device triggers an event message.
Settings
Parameters
Temperat...ing
<<
<
>
>>
Hot-spot
Top oil
Ambient
Bottom oil
OLTC
GP 1
GP 2
GP 3
GP 4
-
-
117.0 °C
122.0 °C
90.0 °C
105.0 °C
-20.0 °C
-25.0 °C
50.0 °C
60.0 °C
-20.0 °C
-30.0 °C
90.0 °C
105.0 °C
-20.0 °C
-25.0 °C
100.0 °C
110.0 °C
-20.0 °C
-25.0 °C
95.0 °C
100.0 °C
-20.0 °C
-30.0 °C
95.0 °C
100.0 °C
-20.0 °C
-30.0 °C
95.0 °C
100.0 °C
-20.0 °C
-30.0 °C
95.0 °C
100.0 °C
-20.0 °C
-30.0 °C
95.0 °C
100.0 °C
-20.0 °C
-30.0 °C
95.0 °C
100.0 °C
-20.0 °C
-30.0 °C
95.0 °C
100.0 °C
-20.0 °C
-30.0 °C
95.0 °C
100.0 °C
-20.0 °C
-30.0 °C
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
04.02.2020 11:14
Figure 165: Temperature monitoring
1. Go to
Settings > Parameters > Temperature monitoring
.
2. Select the desired parameter.
3. Set the desired parameter.
4. Press the
Accept
button to save the modified parameter.
9.22.10 Switching interval monitoring
You can use this function to monitor the typical tap-change behavior of your
transformer.