9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
278
6385142/08 EN
ETOS
®
ED
For the Duval, Rogers, Dörnenburg and IEC 60599 analyses, the values
measured by the sensor have to exceed the following detection limits. If the
measured values are less than the detection limit, the device will use the de-
tection limit value for the calculation.
Gas
Detection limit
H
2
50 ppm
CH
4
10 ppm
C
2
H
2
10 ppm
C
2
H
4
10 ppm
C
2
H
6
10 ppm
Table 87: Detection limits
9.27.2.1 Absolute values
You can display the current absolute measured values of the sensors. Fur-
thermore, a bar chart shows a graphical representation of the measured
value and the set limit values (yellow, red).
Figure 202: Display of absolute values
► Go to
Information > Active part > DGA > Absolute values
.