9.31.1 Setting operator interval for OLTC maintenance
You can define the maintenance interval of your choice for the on-load tap-
changer. You can define the maintenance interval as dependent on time
and/or number of tap-change operations. If the limit is reached (100%), the
device triggers an event message (red).
Settings
Parameters
Maintena...tor
Name
Value
Interval type
Deactivated
Number of tap-change operations
150000
Duration
1.0 a
Date of next maintenance
17.09.2066 23:59:21
Event (yellow)
90.0 %
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
04.02.2020 11:14
Figure 224: Maintenance: OLTC operator
1. Go to
Settings > Parameters > On-load tap-changer > Maintenance:
OLTC operator
.
2. Select the desired parameter.
3. Set the desired parameter.
4. Press the
Accept
button to save the modified parameter.