14 Technical data
Maschinenfabrik Reinhausen GmbH 2020
380
6385142/08 EN
ETOS
®
ED
14.3 Technical data for position transmitter equipment
Resistance-type position transmitter module
Standard resistance: 10.0 Ω (0.6 W, +/-1 %) per tap position
The number of desired operating positions determines the number of loaded
resistors.
The decisive power loss of the position transmitter module is 0.6 W because
in the worst-case scenario only one resistor is energized. The supply voltage
should not exceed DC 220 V. If your setup is more demanding, please con-
tact Maschinenfabrik Reinhausen.
Position transmitter module with N/O contact range (break-before-make
contact)
AC: 250 V, 0.5 A (resistive loading)
DC: 220 V, 0.2 A (resistive loading)
Minimum voltage level for signal and data processing: 24 V
Position transmitter module with N/O contact range, (make-before-
break-type)
AC, DC: 250 V, 0.02 A (resistive loading)
AC, DC: 24 V, 0.20 A (resistive loading)
Minimum voltage level for signal and data processing: 24 V
Position transmitter module with N/O contact range, 10 A (make-before-
break-type) for controlling current matching transformer in industrial
applications.
AC, DC: 250 V, 10 A (resistive loading)
Position transmitter module, diode matrix
DC: 220 V, 0.2 A (resistive loading)
Minimum voltage level for signal and data processing: 24 V
14.4 Permissible ambient conditions
Permitted ambient tem-
perature during opera-
tion
Standard
-25...+50 °C
Arctic with thermostat-controlled
additional heating
-40...+50°C
In the temperature
range of -40…+50 °C,
all heaters must be in
operation continuously.
HiTemp
-25…+55 °C