4 Product description
Maschinenfabrik Reinhausen GmbH 2020
49
6385142/08 EN
ETOS
®
ED
4.10.2 Additional operating controls and display elements when using
the MControl touch panel (optional)
If you are using the device with the optionally available MControl touch
panel, additional operating controls and display elements are displayed on
the left edge of the screen. Depending on the device configuration, a variety
of keys are available:
Figure 31: Additional display elements and operating controls
Status
LED status
Status display
1)
REMOTE key
Select the operating mode:
▪ On: REMOTE
▪ Off: LOCAL
2)
AVR AUTO key
Activate auto mode.
2)
RAISE key
Send a control command to the motor-drive
unit to increase the voltage. Only possible in
manual mode.
2)
AVR Manual key
Activate manual mode.
2)
LOWER key
Send a control command to the motor-drive
unit to reduce the voltage. Only possible in
manual mode.
1)
Not available if local/remote is toggled using a digital input.
2)
Only available in the "Automatic voltage regulation" function package.
4.10.3 Operating concept
You can operate the device using the controls on the front panel or using the
web-based ISM™ Intuitive Control Interface visualization on a PC. The
scope of function and structure of both options is virtually identical.