9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
124
4453918/14 EN
ETOS
®
TD
Periodic mode: Switch-on delay
You can use this parameter to set the time period after which the cooling
stages are to be switched back on again.
9.10.6 Configuring alternating mode
If the transformer is equipped with several similar cooling stages, you can
run the stages in alternating mode. In alternating mode, each of the cooling
stages is run in turn to evenly distribute the load of the cooling stages. You
can activate/deactivate alternating mode individually for every cooling stage
(Configuring cooling stages [
Only use alternating mode for similar cooling stages.
Example: If you activate alternating mode for 2 cooling stages and set a
change interval of 24 h, then cooling stage 1 is switched off after 24 h and
cooling stage 2 is switched on. After another 24 h, cooling stage 2 is
switched off and cooling stage 1 is switched on, etc.
Settings
Parameters
Cooling ...rol
Name
Value
Operating mode
Manual
Load-dep. mode
Off
Load-dep. mode: Switching point
100.0 %
Load-dep. mode: Switch-on delay
2.0 min
Load-dep. mode: Overrun time
30.0 min
Activate period. mode
Off
Period. mode: Interval
24 h
Period. mode: Switch-on duration
30 min
Period. mode: Switch-on delay
120 min
Activate altern. mode
Off
Altern. mode: Change interval
24 h
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
04.02.2020 10:14
Figure 89: General cooling
1. Go to
Settings > Parameters > Cooling system > Cooling system con-
trol
.
2. Select the desired parameter.
3. Set the parameter.
4. Press the
Accept
button to save the modified parameter.
Activate alternating mode
You can use this parameter to activate the alternating mode of the cooling
system control.