9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
134
4453918/14 EN
ETOS
®
TD
Oil pressure
You can use these parameters to set the limit values for the permissible
pressure of the oil circuit. You can set two lower limit values for each cooling
stage.
Oil flow
You can use these parameters to set the limit values for the permissible flow
rate of the oil circuit. You can set two lower limit values for each cooling
stage.
Oil pump current
You can use these parameters to set the limit values for the permissible cur-
rent consumption of the oil circuit pump. You can set two upper and two
lower limit values for each cooling stage.
Feed water temperature
You can use these parameters to set the limit values for the permissible feed
temperature of the water circuit. You can set two upper and two lower limit
values for each cooling stage.
Return water temperature
You can use these parameters to set the limit values for the permissible re-
turn temperature of the water circuit. You can set two upper and two lower
limit values for each cooling stage.
Water pressure
You can use these parameters to set the limit values for the permissible
pressure of the water circuit. You can set two lower limit values for each
cooling stage.
Water flow
You can use these parameters to set the limit values for the permissible flow
rate of the water circuit. You can set two lower limit values for each cooling
stage.
Water pump current
You can use these parameters to set the limit values for the permissible cur-
rent consumption of the water circuit pump. You can set two upper and two
lower limit values for each cooling stage.