9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
146
4453918/14 EN
ETOS
®
TD
2. Select the option you want.
3. Press the
Accept
button to save the modified parameter.
TDSC Umax/Umin
You can use these parameters to set the maximum and minimum desired
value. The maximum or minimum desired value is activated when the mea-
sured active power reaches the set minimum or maximum active power.
1. Go to
Settings > Parameters > Control > TDSC Umax/Umin
.
2. Enter maximum/minimum desired value.
3. Press the
Accept
button to save the modified parameter.
TDSC U0
You can use this parameter to set the desired value which is to be used
when the measured active power is 0.
1. Go to
Settings > Parameter > Control > TDSC U0
.
2. Enter desired value at active power 0.
3. Press the
Accept
button to save the modified parameter.
TDSC Pmax/Pmin
You can use these parameters to set the maximum and minimum active
power value at which the maximum and minimum active power-dependent
desired value is to be used for regulation.
1. Go to
Settings > Parameters > Control > TDSC Pmax/Pmin
.
2. Enter active power for maximum/minimum desired value.
3. Press the
Accept
button to save the modified parameter.
9.15.1.7 Active power-dependent adjustment of desired voltage value with 3
different desired values
The TAPCON® Dynamic Setpoint Control (TDSC) function is used to adapt
the desired voltage value depending on the measured active power. This al-
lows you to compensate for a voltage drop during increased load or an in-
crease in voltage due to a decentralized feed-in.
The device provides you with 3 different sets of parameters for this purpose.
Depending on the selection of the desired value 1, 2 or 3, the device uses
the parameter set 1, 2 or 3 for TDSC.