9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
207
4453918/14 EN
ETOS
®
TD
The following parameters are available for setting function monitoring:
▪ Function monitoring
▪ Hysteresis
▪ Delay time
Settings
Parameters
U bandwidt...ing
Name
Value
Function monitoring
Auto and Manual
Hysteresis
0.0 %
Delay time
15 min
Lower bandwidth hysteresis
0.1 %
Lower bandwidth delay time
2 s
Upper bandwidth hysteresis
0.1 %
Upper bandwidth delay time
2 s
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
23.09.2020 09:23
Figure 139: Q bandwidth monitoring
1. Go to
Settings > Parameters > On-load tap-changer regulator > Q
bandwidth monitoring
.
2. Select the desired parameter.
3. Set the desired parameter.
4. Press the
Accept
button to save the modified parameter.
Function monitoring
You can use this parameter to activate function monitoring. You can select
the following options:
Setting
Behavior
Off
Function monitoring is deactivated.
Only Auto
Function monitoring is only active in AVR AUTO oper-
ating mode.
Auto and Manual
Function monitoring is active in AVR AUTO and AVR
MANUAL operating modes
Table 72: Activate function monitoring
Hysteresis
You can use this parameter to set the hysteresis. You can use this to avoid
the unnecessary generation of messages if the measured value fluctuates
around a threshold value.