9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
115
4453918/14 EN
ETOS
®
TD
You can link the event messages with device functions, digital outputs, and
control system messages. You can also link all other event messages (e.g.
Undervoltage U<
) with digital outputs and control system messages. Corre-
sponding parameters, for which you need to enter the relevant event num-
ber, are provided for this purpose.
9.9.1 Linking functions
You can link the
Generic digital input
or
Generic SCADA command
events
with device functions. This allows you to remotely control the device using
digital inputs or commands via the control system (SCADA). Depending on
your device configuration, various functions are available for this purpose via
parameters.
In order to establish the link, you have to enter the corresponding event
number in the desired parameter.
Note that you can only enter the event numbers of the
Generic digital input
or
Generic SCADA command
events.
If you enter event number 500, the link is disabled.
Settings
Parameters
Link functions
Name
Value
Master parallel operation method
500
Follower parallel operation metho...
500
Parallel op. meth. auto. tap sync...
500
Independent regulation
500
Blocking
500
High-speed return
500
Target-tap-position operation
500
Activate desired value 1
500
Activate desired value 2
500
Activate desired value 3
500
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
04.02.2020 11:14
Figure 83: Linking functions
ü
The desired event number is known.
1. Go to
Settings > Parameters > System > Link functions
.
2. Select the desired parameter.
3. Enter the desired event number.
4. Press the
Accept
button to save the modified parameter.
Master parallel operation method
If the assigned event is active, the device activates the master parallel oper-
ation method.