Load-dependent mode: Overrun time
You can use this parameter to set the time period for which the cooling
stages remain switched on when the transformer load current returns to a
value below the set switching point.
9.10.5 Configuring periodic mode
Periodic mode is used to prevent the bearings of the cooling stages from
seizing up as a result of long idle periods. To do this, the cooling stages are
operated for a certain period at regular intervals regardless of the measured
temperature. You can activate/deactivate periodic mode individually for ev-
ery cooling stage (Configuring cooling stages [
Settings
Parameters
Cooling ...rol
Name
Value
Operating mode
Manual
Load-dep. mode
Off
Load-dep. mode: Switching point
100.0 %
Load-dep. mode: Switch-on delay
2.0 min
Load-dep. mode: Overrun time
30.0 min
Activate period. mode
Off
Period. mode: Interval
24 h
Period. mode: Switch-on duration
30 min
Period. mode: Switch-on delay
120 min
Activate altern. mode
Off
Altern. mode: Change interval
24 h
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
04.02.2020 10:14
Figure 88: Cooling system control
1. Go to
Settings > Parameters > Cooling system > Cooling system con-
trol
.
2. Select the desired parameter.
3. Set the parameter.
4. Press the
Accept
button to save the modified parameter.
Activate periodic mode
You can use this parameter to activate the periodic mode of the cooling sys-
tem control.
Periodic mode: Interval
You can use this parameter to set the time period after which the cooling
stages are to be switched on for the first time.
Periodic mode: Switch-on duration
You can use this parameter to set the length of time that the cooling stages
are to be switched on for.