TD
CPU-COM2
MSENSE DGA 9
D0 (A)
D1 (B)
Com. (C)
1
2
3
4
5
6
7
8
9
(PhoneB)
(GND)
X304:5a
X304:4b
X304:3
X304:1a
X304:1b
(OUTA)
(OUTB)
(PhoneA)
Figure 43: Connection example MSENSE® DGA 9 (terminal X304)
6.4.2 MESSKO® MTeC® EPT303 FO
If you would like to use a MESSKO® MTeC® EPT303 FO sensor, you must
connect the sensor to the RS485 plug terminals on the sensor bus. Use a
shielding clamp to apply the shield to the cable. You can directly connect ad-
ditional MESSKO® MTeC® EPT303 FO sensors to the plug terminal.
The EPT303 FO sensor module contains a terminating resistor. If you would
like to use the EPT303 FO sensor together with other sensor types on an
MR sensor bus, then we recommend connecting the EPT303 FO sensor to
the end of the bus.
CPU-COM2
EPT303 FO
D0 (A)
D1 (B)
Com. (C)
1
2
3
4
5
6
7
8
9
D+ (B)
GND
D- (A)
D+ (B)
GND
D- (A)
1
2
3
4
5
6
1
6
Figure 44: Connection example MESSKO® MTeC® EPT303 FO (terminal RS485)