5 Installation and commissioning
31
BA5831400-00 EN
1. Immerse the temperature sensor of the pointer thermometer and a cali-
brated glass thermometer in the liquid bath for approx. 15 minutes.
2. Compare the measured temperature values of the pointer thermometer
and glass thermometer with each other.
ð
If the measured temperature values deviate from each other significantly
(maximum permitted deviation ±3°C), contact the service department of
Maschinenfabrik Reinhausen GmbH [
5.3 Mounting the pointer thermometer
5.3.1 Attaching the pointer thermometer to the transformer
When attaching the thermometer to the transformer, note the following infor-
mation:
▪ Ensure that the pointer thermometer is mounted vertically.
Figure 10: Mounting position
▪ Ensure that the pointer thermometer is not subjected to any vibrations at
the installation location.
▪ Comply with EMC standards [
▪ Observe the dimensions in the chapter Technical data [