5 Installation and commissioning
65
BA5831400-00 EN
The heating current is measured indirectly using the voltage drop at the in-
ternal 1Ω resistor. The relationship I = U/R produces the result that, at
R = 1 Ohm, the numerical value of the measured voltage directly corre-
sponds to the numerical value of the heating current. The heating current
can be adjusted by setting the potentiometer P.
I
I
W
H
P
R1Ω
V
6
5
4
3
Figure 48: Circuit
I
W
Secondary transformer current
I
H
Heating current
P Potentiometer
V Voltage measurement