5 Installation and commissioning
67
BA5831400-00 EN
1. Write down the temperature currently displayed (e.g. 30 °C).
2. Connect a constant current source to terminals
and
.
Figure 50: Connecting the current source
3. Set the nominal secondary transformer current I
w
(e.g. 2 A) on the current
source.
Determining the heating current
ü
The value of the temperature gradient is specified by the transformer
manufacturer (e.g. gr = 20 K).
1. Read the associated value for the heating current from the setting curve
(desired value, 1.1 A in this example).
2. Determine the voltage at terminals
and
using a high-impedance
voltmeter.
ð
The numerical value of the measured voltage in
V
corresponds to the
numerical value of the heating current in
A
.