TAPMOTION® TD ISM®
Installation and commissioning
This chapter describes how to correctly connect and commission the OEM
Control Box.
WARNING
Risk of severe injury or death!
An energized transformer and energized on-load tap-changer components
can cause death or serious injuries when installing the motor-drive unit!
► Ensure de-energized state of transformer and on-load tap-changer
components during the installation of the motor-drive unit.
You may only connect the OEM Control Box to circuits with an external over-
current protection device and an isolating device with all poles disconnected
so the equipment can be fully de-energized if required (service, maintenance
etc.).
Suitable equipment includes isolating devices in accordance with IEC
60947-1 and IEC60947-3 (e.g. circuit breaker). When selecting the circuit
breaker type, note the properties of the relevant circuits (voltage, maximum
currents). Please also note the following:
▪
It must be easy for the operator to access the isolating device
▪
The isolating device must be labeled for the device circuits to be isolat-
ed
▪
The isolating device must not be part of the power line
▪
The isolating device must not interrupt the main grounding conductor
You must fuse the power supply circuit with a C16A type miniature circuit
breaker.
To install and commission the OEM Control Box, proceed as follows:
1.
Connect the connecting lead to the gear motor's plug connector.
2.
Connect OEM Control Box to the power supply.
The CEE plug for the OEM Control Box power supply is configured for a
clockwise rotary field.
5