6 Functions and settings
Maschinenfabrik Reinhausen GmbH 2016
100
5163667/00 EN
TRAFOGUARD® ISM®
Circuit D
▪
The voltage transformer VT is connected to the phase conductors L1
and L2.
▪
The current transformer CT is looped into the phase conductor L3.
▪
The current I
L3
is ahead of voltage U
L1
-V
L2
by 90°.
▪
The voltage drop on a phase conductor is determined by the current I
L3
.
If you use this circuit, set the device as follows:
Parameter
Option
Voltage-transformer circuit
3 Ph differential voltage
Current-transformer circuit
3 Ph phase current
Phase angle correction
90°
Table 17: Circuit D
Circuit E
▪
The voltage transformer VT is connected to the phase conductors L1
and L2.
▪
The current transformer CT is looped into the phase conductor L2.
▪
The current I
L2
is ahead of voltage U
L2
-U
L1
by 30°.
▪
The voltage drop on a phase conductor is determined by the current I
L2
.
If you use this circuit, set the device as follows: