6 Functions and settings
Maschinenfabrik Reinhausen GmbH 2016
159
5163667/00 EN
TRAFOGUARD® ISM®
Configuring IEC 60870-5-101 (optional)
If you want to use the IEC 60870-5-101 control system protocol, you must
set the following parameters.
Figure 122: Setting parameters for IEC60870-5-101
Serial interface
You can use this parameter to select the serial interface for data transmis-
sion. You can select the following options:
▪
RS232
▪
RS485
To select the serial interface, proceed as follows:
1.
Go to
Settings > Parameters > IEC
60870-5-101 > Serial interface
.
2.
Select serial interface.
3.
Press the
Accept
button to save the modified parameter.
Baud rate
You can use this parameter to set the serial interface's baud rate. You can
select the following options:
▪
9600 baud
▪
19200 baud
▪
38400 baud
▪
57600 baud
▪
115200 baud
To set the baud rate, proceed as follows:
1.
Go to
Settings > Parameters > IEC
60870-5-101 > Baud rate
.
2.
Select baud rate.
3.
Press the
Accept
button to save the modified parameter.